3
200 A Fused Loadbreak Elbow Connector Replacement Fuse
InstallatIon InstructIons
MN132021EN November 2016
Probe and Elbow Housing Disassembly
Step 3
After a visible ground is achieved on both sides of the
fuse, remove the Fused Loadbreak Elbow Connector from
feedthru device.
Step 4
Install supplied wire probe wrench into wrench hole of
loadbreak probe. Turning counterclockwise, unthread and
remove loadbreak probe from fused loadbreak elbow.
Remove Loadbreak Probe
Wire
Probe
Wrench
Drain Wires
Turn Counterclockwise
to loosen
Step 5
Detach drain-wire lead from the drain-wire eye of the
elbow housing. At the overlap of elbow housing and cable
housing, insert supplied bleeder strap approx. 1/2
"
(13
mm) under lip of elbow housing. Slide strap around the
entire circumference of fused loadbreak elbow to vent
the interfaces. Leave the bleeder strap inserted between
housings.
Cable Housing
Bleeder Strap
Elbow Housing
Probe Removed
Elbow and Cable Housing Overlap