background image

Installation, Operation & Maintenance Manual

 

Control Panels for Automatic Self-Cleaning Strainers

 

Model 596 and Model 2596

 

IOM  

Controls 04/2020

 

REV B.

 

Page 

 2 

of 9

 

Eaton  Filtration LLC, 

44 Apple 

Street, Tinton  Falls, 

NJ 

07724     www.eaton.com/filtration    

Phone: 

732-212-4700

 

 

 

 

RECEIVING, HANDLING AND INSPECTION

 

The control panel, motor and accessories have been packed 
in a separate container but shipped with the strainer. This 
provides protection from damage during 
transit and also provides for ease of storage if the controls are 
not installed immediately. When first received the following 
must be done: 

 

1.  Unpack and inspect for damage. 

 

2.  Report any damage to carrier immediately. 

 

3.  If controls are not installed at this time, refer to Storage 

Instructions. 

 

STORAGE INSTRUCTIONS

 

 

Repack all components in the original carton and reuse all 
protective packaging. Store all components in an indoor, 
clean, and dry environment. Protect from temperature 
extremes. Mark cartons to protect from handling abuse. 

 

STRAINER MODE OF OPERATION 

CONTINUOUS BACKWASH

 

 

This is the most effective way to keep the strainer element 

clean

 and have the least pressure loss. Continuous element 

washing can be accomplished with a minimum of control 
devices. However, it offers no flexibility of operation when 
there are significant changes in flow volume or solids content 
of the fluid. 

 

The 

“d

rain

 line requires a blow-down/drain valve which may 

be manually operated. Normal valve position is CLOSED. 

 

The backwash line requires a backwash valve which may be 
manually operated on the backwash line. Normal valve 
position is FULL OPEN. 

 

The backwash motor requires a motor starter. Furnish with 
overload protection and fused disconnect. 

STRAINER MODE OF OPERATION 

AUTOMATIC BACKWASH (TIMED CYCLE)

 

 

The preferred mode of operation for a self-cleaning strainer is 
one where the control system will permit both intermittent and 
continuous backwash as required by operating conditions. 

 

The 

“d

rain

 line requires a blow-down/drain valve which may 

be manually operated. Normal valve position is CLOSED. 

 

The backwash line requires a backwash valve, either electrically 
or pneumatically operated on the backwash line. This valve 
should operate only in the FULL OPEN or FULL CLOSED position. 

 

A fully adjustable differential pressure switch is furnished to 
detect the increase of pressure across the strainer. It will 
activate a backwash cycle independent of the time-controlled 
sequence. NOTE: Set switch at 2psi over the observed clean 
pressure drop. 

 

Eaton provides a control panel, containing all necessary relays, 
timers, lights, switches, etc. This will initiate and monitor the 
intermittent backwash cycles. 

 

VALVE SELECTION

 

 

Several important factors to consider when selecting the 
necessary valves. 

 

Valve Type: Gate, plug, and butterfly valves  can be used. 
However, ball valves provide the most advantages. Ball valves, 
when 

Full Open

 provide a uniform and straight flow path 

minimizing pressure loss. Since only 90° rotation of the stem is 
required to go from 

Fully Closed

 to 

Fully Open

 motorized 

operators are easily adapted and provide short cycle times. 

 

Valve Material: Iron, bronze, steel, and stainless steel are the 
most common. Select valve and trim material that will not 
corrode or react with the process fluid or the environment. 

 

Pressure Rating: Select the valve class with a pressure rating 
equal to or greater than the system design pressure. 

 

Connection: Select a valve with end connections (flanged, 
threaded, etc.) that will provide ease of maintenance and 
trouble-free service. 

Summary of Contents for 2596

Page 1: ... Timed Cycle 2 Valves 2 Valve Selection 2 Backwash Blow Down Drain Valve 3 Electric Actuators 3 Pneumatic Actuators 3 Differential Pressure Switches 4 Switch Description 4 Mounting Piping and Wiring 4 Adjustment 4 Control Panel 5 Description 5 Cycle Time Sequence 5 Standard Features 5 Operating Modes 6 Changing Backwash Timer Settings 6 SmartWire DT Error Messages 7 System Error Messages 7 Electri...

Page 2: ...d protection and fused disconnect STRAINER MODE OF OPERATION AUTOMATIC BACKWASH TIMED CYCLE The preferred mode of operation for a self cleaning strainer is one where the control system will permit both intermittent and continuous backwash as required by operating conditions The drain line requires a blow down drain valve which may be manually operated Normal valve position is CLOSED The backwash l...

Page 3: ...PNEUMATIC ACTUATORS A double acting piston design that uses a clean air supply of 40 125 psi pressure powers the actuator properly Using an electric signal a solenoid pilot valve controls the air supply to the actuator Most actuators have pipe thread connections NPT located so that the solenoid valves may be mounted with minimal tubing runs Customer must run wiring and conduit from the control pan...

Page 4: ...ure connections furnished on the inlet discharge nozzles of the strainer as shown in Fig 1 Customer must supply and run wiring and conduit between the differential pressure switch and the control panel See Fig 2 for wiring connections DIFFERENTIAL SWITCH ADJUSTMENT While it is possible to use other equipment than what is described below any installation should have the items described here Equipme...

Page 5: ... supply The ACS line of control panels allows operation either in the Manual or Auto modes In the Manual mode the strainer will continuously backwash In the Auto mode the strainer is allowed to backwash according to the preset timing cycle or when the differential pressure switch is activated NOTE The customer determines the timing cycle length and changes it as required The control logic protects...

Page 6: ... closes then HIGH DIFFERENTIAL indicator illuminated HI DP alarm contact closes AUTO MODE Timer range limits for BACKWASH ON valve open is 1 to 1440 minutes Timer range limits for BACKWASH OFF valve closed is 1 to 1440 minutes CHANGING THE BACKWASH TIMER SETTINGS To change timer settings press ALT button Use the UP or DOWN arrow buttons to move the cursor to select lines BW Open SP or BW Close SP ...

Page 7: ...errors If a hardware error occurs the screen will display what device and node is damaged or disconnected If more than one node is damaged or disconnected the screen will cycle though all errors present SYSTEM ERROR MESSAGES Motor Overload If there is a motor overload the following message will flash on the screen Hi DP Backwash Hi DP backwash is indicated by the red LED and with a change of state...

Page 8: ...ge 8 of 9 Eaton Filtration LLC 44Apple Street Tinton Falls NJ 07724 www eaton com filtration Phone 732 212 4700 Installation Operation Maintenance Manual Control Panels for Automatic Self Cleaning Strainers Model 596 and Model 2596 ...

Page 9: ...ranca São Paulo SP 05038 001 Brazil Tel 55 11 3616 8461 For more information please email us at filtration eaton com or visit www eaton com filtration 2020 Eaton All rights reserved All trademarks and registered trademarks are the property of their respective owners All information and recommendations appearing in this brochure concerning the use of products described herein are based on tests bel...

Reviews: