Network Management Card
– User Manual
34003991EN/EB
Page
112/118
8.2 SNMP objects
8.2.1 MGE MIB
The NMC card implement reduce MGE Office Protection Systems MIB, with the objects bellow managed.
The entire MIB description is available on
www.mgeops.com
area “
Downloads – Software Download
.
Le chemin d’accès à la MIB MGE est 1.3.6.1.4.1.705.1.
MIB object
SNMP Format
Add.path
upsmgIdentFamilyName
String
{1,1,0}
upsmgIdentModelName
String
{1,2,0}
upsmgIdentFirmwareVersion
String
{1,4,0}
upsmgIdentSerialNumber
String
{1,7,0}
upsmgConfigLowBatteryTime
seconds
{4,7,0}
upsmgConfigLowBatteryLevel
%
{4,8,0}
upsmgConfigAutoRestart
1(yes) 2(no)
{4,9,0}
upsmgConfigVARating
VA
{4,12,0}
upsmgBatteryRemainingTime
seconds
{5,1,0}
upsmgBatteryLevel
%
{5,2,0}
upsmgBatteryVoltage
deciVolts
{5,5,0}
upsmgBatteryCurrent
deciAmps
{5,6,0}
upsmgBatteryFaultBattery
1(yes) 2(no)
{5,9,0}
upsmgBatteryReplacement
1(yes) 2(no)
{5,11,0}
upsmgBatteryLowBattery
1(yes) 2(no)
{5,14,0}
upsmgBatteryChargerFault
1(yes) 2(no)
{5,15,0}
upsmgBatteryLowCondition
1(yes) 2(no)
{5,16,0}
upsmgInputPhaseNum
{6,1,0}
mginputVoltage_1
DeciVolts
{6,2,1,2,1,0}
mginputVoltage_2
DeciVolts
{6,2,1,2,2,0}
mginputVoltage_3
DeciVolts
{6,2,1,2,3,0}
mginputFrequency_1
DeciHz
{6,2,1,3,1,0}
mginputFrequency_2
DeciHz
{6,2,1,3,2,0}
mginputFrequency_3
DeciHz
{6,2,1,3,3,0}
mginputMinimumVoltage
{6,2,1,4,0}
mginputMaximumVoltage
{6,2,1,5,0}
mginputCurrent_1
DeciAmps
{6,2,1,6,1,0}
mginputCurrent_2
DeciAmps
{6,2,1,6,2,0}
mginputCurrent_3
DeciAmps
{6,2,1,6,3,0}
upsmgInputBadStatus
{6,3,0}
upsmgInputLineFailCause
{6,4,0}
upsmgOutputPhaseNum
{7,1,0}
mgoutputPhaseIndex_1
{7,2,1,1,1,0}
mgoutputPhaseIndex_2
{7,2,1,1,2,0}
mgoutputPhaseIndex_3
{7,2,1,1,3,0}
mgoutputVoltage_1
deciVolts
{7,2,1,2,1,0}
mgoutputVoltage_2
deciVolts
{7,2,1,2,2,0}
mgoutputVoltage_3
deciVolts
{7,2,1,2,3,0}