Network Management Card
– User Manual
34003991EN/EB
Page
91/118
7.4 JBUS table
7.4.1 Data for Pulsar 700 / 1000 / 1500
7.4.1.1 Status table
Status description
Status to 0
Status to 1
Word (hex)
Bit
Load protected
no
yes
40
0
UPS coupled
no
yes
40
1
Unit general alarm
no
yes
40
2
UPS in backup
no
yes
40
4
Battery low warning
no
yes
40
5
Low battery
no
yes
40
6
Operation on static switch
no
yes
40
7
Communication fault
absent
present
40
9
UPS overload
no
yes
40
A
Emergency stop
absent
present
40
B
Battery to be checked
no
yes
40
D
Device ventilation fault
no
yes
40
E
Battery present
absent
present
42
0
Mains 1 voltage out of tolerance
no
yes
44
8
Mains 1 frequency out of tolerance
no
yes
44
B
Bypass status
no
yes
46
7
Charger general fault
no
yes
49
0
Battery charge
not in
charge
in charge
49
1 & 3
Converter fault
no
yes
4A
1
Inverter fault
no
yes
4C
1