3.

Select

EcoControl function detection threshold

. The EcoControl function

detection threshold panel displays.

4.

If the peripherals connected to the EcoControl outlets do not turn off when the
load powered by the Master outlet is turned off or is in standby mode, set the
detection threshold value to

High

.

5.

If the peripherals connected to the EcoControl outlets turn off when the load
powered by the Master outlet is working normally, set the detection threshold
value to

Low

.

6.

Click

Apply

to activate, or click

OK

to activate and the close window.

7.

Restart the load connected to the Master outlet.

Indicators

1

2

3

4

6

5

7

8

1.

On/Off Button

Button that controls power to the UPS and initiates the self-test function.

S

Press the On/Off button to turn on the UPS.

S

Press the On/Off button again to turn off the UPS.

The UPS performs a self-test for about 5 seconds when the UPS is turned on.

2.

Fault/Warning (Red) LED

Indicates that a fault or warning condition is present.

S

A flashing red LED indicates that a Site Wiring Fault exists.

S

A solid illuminating red LED indicates that an internal UPS fault exists, or that
the battery should be replaced.

3. Surge Protection Outlets

Output receptacles that provide surge and spike protection only.

S

350–550 VA models have four 5-15R surge protection outlets.

S

750 VA model has five 5-15R surge protection outlets.

4. Battery Backup and Surge Protection Outlets

Output receptacles that provide both backup and surge protection.

S

350–550 VA models have four 5-15R backup and surge protection outlets.

S

750 VA model has five 5-15R backup and surge protection outlets.

5. Modem/Phone/DSL/Fax Surge Protection Ports

A modem or Ethernet data line can be protected against surges by connecting
it through the UPS. Connect the device cable between the wall outlet and the
UPS, and use a similar cable between the UPS and the device.

6. USB Communication Port (450 VA, 550 VA, and 750 VA models only)

The built-in USB port connects to your computer (with the provided USB cable).
The Personal Solution-Pac monitoring and shutdown software can be
configured to automatically save your files and shut down your computer in the
event of a prolonged power outage. Your computer can receive the status of
utility power line, utility power failure, on battery, and low battery by contact
closure signals that are sent through the USB port.

7. Circuit Breaker (resettable)

The circuit breaker button protrudes when the overload condition occurs. If the
button protrudes, disconnect some of the non-essential equipment and reset
the circuit breaker by pressing the button in.

8. Input Power Cord

Six-foot line cord.

Replace Battery

Turn the UPS over and press in the
release tab. Slide the battery cover
off the UPS.

Connect the battery wires firmly to the
replacement battery terminals; red to
positive (+), black to negative (–). Insert the
replacement battery into the battery
compartment.

3

Slide the battery cover on the UPS until
the release tab locks into place.

2

Pull out the battery and disconnect
the battery wires.

4

1

Turn off the UPS and disconnect the
UPS from the power source.

5

Service and Support

For questions and/or problems, please call your local distributor or the Eaton
Customer Support Center at one of the following telephone numbers and ask for a
UPS technical representative.

United States:

1.800.356.5737

Europe, Middle East, and Africa:

+44.17.53.608.700

Asia:

+852.2830.3030

Australia:

+61.3.9706.5022

Please have the following information ready when you call the Eaton Customer
Support Center: Model number, serial number, symptoms of failure or problem,
customer return address, and contact information. If repair is required, you will be
given a Returned Material Authorization (RMA) Number. This number must appear
on the outside of the package and on the Bill of Lading (if applicable). Use the
original packaging or request packaging from the Eaton Customer Support Center
or distributor. Units damaged in shipment as a result of improper packaging are not
covered under warranty. A replacement unit will be shipped, freight prepaid for all
units under warranty. For additional information please visit us online at

www.eaton.com/powerquality

.

Specifications

Model

3S350

3S450

3S550

3S750

UPS Power

350 VA / 200W

450 VA / 270W

550 VA / 330W

750 VA / 450W

Input Voltage Range

96V–138V, adjustable to 75V–144V through Personal Solution-Pac

Input Frequency

50/60 Hz (46–70Hz working range)

Voltage/Frequency of
Battery Backup Outlets in
Battery Mode

115V +15% -20% / 50–60Hz

±

1%

Input Protection

10A resettable

circuit breaker

12A resettable circuit breaker

Transfer Time

5 ms typical

Phone / ISDN / ADSL /
Ethernet Surge Protection

RJ-45

Sealed Lead Acid Battery

12V, 4.5Ah

12V, 4.5Ah

12V, 5Ah

12V, 9Ah

Operating Temperature

0

°

C to 40

°

C (32

°

F to 104

°

F)

Storage Temperature

-2.5

°

C to + 55

°

C (28

°

F to 131

°

F)

Operating Relative
Humidity

0 to 85% noncondensing

Safety Standards

UL 1778

Electromagnetic
Compatibility Standards

FCC Part 15 Class B

UPS Dimensions
(H

×

W

×

D)

335

×

140

×

86 mm

(13.2

×

5.5

×

3.4

)

335

×

170

×

86 mm

(13.2

×

6.7

×

3.4

)

UPS Weight

2.9 Kg (6.4 lb)

4.2 Kg (9.3 lb)

Troubleshooting

Problem

Diagnostic

Solution

The Fault/Warning LED
flashes red immediately
after plugging the UPS into
a wall outlet.

A Site Wiring Fault has
occurred. The outlet that the
UPS is plugged into is not
properly grounded or
properly wired.

Have a qualified electrician
correct the wiring.

The outlets are not
powered.

The wall outlet is not
powered.

Supply power to the wall outlet.

The circuit breaker has been
tripped by an overload on the
UPS output.

Reduce the amount of equipment
plugged into the UPS and press
the circuit breaker in to reset.

The On/Off button flashes
green and the audio alarm
beeps.

The UPS frequently operates
on battery power because
the AC power source is of
poor quality.

Have the electrical installation
checked by a professional or use
another wall outlet.

The On/Off button flashes
green and the audio alarm
beeps continuously.

The UPS battery backup
outlets are overloaded.

Disconnect excess equipment
connected to the battery backup
outlets.

AC power is available, but
the UPS operates on
battery power.

The UPS circuit breaker
tripped due to an overload
on the UPS output.

Reduce the amount of equipment
plugged into the UPS and press
the circuit breaker in to reset.

Battery backup outlets are
not powered.

The On/Off button is not
illuminated.

Press the On/Off button and verify
that it illuminates green.

The connected devices are
not powered when AC
power fails.

The devices are connected
to the Surge Protection only
outlets.

Connect the devices to the Battery
Backup outlets.

The telephone line is
disturbed or modem
access is not possible.

Surge protection on the
telephone line is no longer
provided.

Disconnect the telephone line
from the wall outlet and contact
your service representative.

The Fault/Warning LED
illuminates red.

The battery has reached the
end of its service life.

Replace battery.

The Fault/Warning LED
illuminates red and the
audio alarm beeps every
30 seconds.

A fault has occurred on the
UPS. The battery backup
outlets are not powered.

Contact your service
representative.