 (Battery mode)

(Bypass mode)

 

The battery LED indicators are turned on and the line LED is turned off. Battery 
supplies power to the load. 

 

In battery mode, the bu

zz

er beeps once every 4 seconds, press the function button 

more than 2 seconds to silence the audible alarm.

4.3 Shut down

 

Press the 

OFF

 button more than 1 second to shut down the UPS.

 

The terminal still have live voltage via bypass, and LED status is as follows.

• 

In bypass mode, the bypass LED indicator is lit and the buzzer beeps once every 2 

minutes, press the function button more than 2 seconds to silence the audible alarm.

 

To completely power down the UPS, disconnect the line input of the UPS.

Summary of Contents for 3C-10000F

Page 1: ...EATON UPS ON LINE 6 20KVA...

Page 2: ......

Page 3: ...1 2 3 4 5 UPS 6 7 1 2 UPS UPS 3 1 UPS 2 3 4 A B C D E 5 6 7...

Page 4: ...1 A 0 40 20 90 B C 2 UPS 25 55 UPS 0 2...

Page 5: ...2 2 1 3 2 1 4 4 2 7 2 1 7 2 2 8 2 3 UPS 9 2 4 12 2 5 14 2 6 15 2 7 23 2 8 EPO 25 2 9 25 2 10 26 3 LCD 27 3 1 27 3 2 28 3 3 28 3 4 30 3 5 31 3 6 31 3 7 31 3 8 33 4 LED 34 4 1 34 4 2 36 4 3 37 4 4 38 4...

Page 6: ...1 1 1 1 UPS UPS UPS UPS ON LINE C 6000FC LCD C 6000FCL LCD C 6000F LED C 6000FL LED C 10000FC LCD C 10000FCL LCD C 10000F LED C 10000FL LED 3C 10000F LED 3C 10000FL LED 3C 20000FL LED...

Page 7: ...2 1 2 1 3 C 6000FC C 6000FCL C 10000FC C 10000FCL C 6000FC C 6000FCL C 6000F C 6000FL C 10000FC C 10000FCL C 10000F C 10000FL C 6000F C 6000FL C 10000F C 10000FL 3C 10000F 3C 10000FL 3C 20000FL...

Page 8: ...3 3C 10000F 3C 10000FL 3C 20000FL EPO POWER OFF RS232...

Page 9: ...W 220VAC 15 25 33A max 60Hz 4Hz 0 99 220 1 56Hz 64Hz 60Hz 0 05 PF 0 8 105 125 1 125 135 30 135 0 1 THD 2 7min 4200W 5min 4200W 7 90 7 90 EMC EMI CNS 14757 2 C3 EMS ESD IEC61000 4 2 Level 4 RS IEC61000...

Page 10: ...W 220VAC 15 25 55A max 60Hz 4Hz 0 99 220 1 56Hz 64Hz 60Hz 0 05 PF 0 8 105 125 1 125 135 30 135 0 1 THD 2 5min 7000w 5min 7000w 7 90 7 90 EMC EMI CNS 14757 2 C3 EMS ESD IEC61000 4 2 Level 4 RS IEC61000...

Page 11: ...0 4 4 Level 4 Surge IEC61000 4 5 Level 4 0 40 25 55 20 90 1000m 3C 10000F 3C 10000FL 3C 20000FL 607 300 820 607 325 936 Kg 136 81 131 KVA KW 10KVA 8KW 20KVA 16KW 220VAC 15 25 55A max 110A max 60Hz 4Hz...

Page 12: ...7 UPS 187V 220V 200V or 208V 10 200 208 220 230 240VAC m 1000 1500 2000 2500 3000 3500 4000 4500 5000 100 95 91 86 82 78 74 70 67 UPS 1000m 2 1 2 2 1 1 UPS 2...

Page 13: ...or 14 mm2 10AWG or 22 mm2 G 12AWG or 14 mm2 10AWG or 22 mm2 6KVA 110V 8AWG 22mm2 10KVA 110V 6AWG 38mm2 3C 10000F 3 C10000FL 3C 20000FL G 10AWG or 22mm2 8AWG or 30 mm2 N 10AWG or 22mm2 6AWG or 38 mm2...

Page 14: ...UPS 2 3 UPS 1 2 UPS 3 110V L1 L2 N1 N2 L1 N2 UPS 110V L N 220V N1 L2 L1 N2 UPS220V L N 4 5 6 9 220V 110V 110V UPS UPS Fig 1 6K 10K 220V...

Page 15: ...10 Fig 4 10K 220V Fig 5 10K 110V Fig 2 6K 10K 110V Fig 3 6K 10K 220V 110V...

Page 16: ...11 Fig 6 10K 220V 110V Fig 8 20K 220V Fig 7 20K 110V Fig 9 20K 220V 110V BATTERY BAT BAT BATTERY BAT BAT BATTERY BAT BAT...

Page 17: ...0 12V 26AH 20 12V 40AH 20 C 6000F C 6000FL 12V 7AH 16 12V 26AH 16 12V 40AH 16 C 10000F C 10000FL C 10000FC C 10000FCL 3C 10000F 3C 10000FL 12V 7AH 20 12V 26AH 20 12V 40AH 20 3C 20000FL 12V 26AH 20 12V...

Page 18: ...13 UPS A 12V 7AH 20 B 12V 26AH 20...

Page 19: ...14 RS232 RS232 UPS 1 RS232 2 RS232 UPS 2 5 UPS DB 9 RS232 2400bps 8bit 1bit None Pin I O 2 RS232 Tx output 3 RS232 Rx input 5 GND output...

Page 20: ...15 1 N X N UPS X UPS UPS X N X 3 UPS N X 2 UPS UPS A UPS UPS 2 6...

Page 21: ...16 B UPS 20 20 UPS 20 10 C UPS UPS D UPS...

Page 22: ...17 E C 6000FC C 6000FCL C 6000F C 6000FL C 10000FC C 10000FCL C 10000F C 10000FL 1 110V 2 220V G N L G G N L L1 N1 L2 N2 G N L L1 N1 L2 N2 G N L L1 N1 L2 N2 L N...

Page 23: ...18 3 220V 110V F 3C 10000F 3C 10000FL 1 110V G N R L1 N1 L2 N2 S T G N R L1 N1 L2 N2 S T G N R L1 N1 L2 N2 S T R S T L N G G N...

Page 24: ...19 2 220V 3 220V 110V G N R L1 N1 L2 N2 S T G N R L1 N1 L2 N2 S T G N R L1 N1 L2 N2 S T R S T N L1 L2 G G N G N R L1 N1 L2 N2 S T G N R L1 N1 L2 N2 S T G N R L1 N1 L2 N2 S T R S T L N G G N...

Page 25: ...20 G 3C 20000FL 1 110V 2 220V...

Page 26: ...21 3 220V 110V...

Page 27: ...22 3 UPS UPS UPS 1 2 UPS UPS 4 1 2 LCD UPS LCD 3 LCD LCD 0 5...

Page 28: ...23 UPS SNMP 2 7 I SNMP UPS AS400 AS400 UPS II AS400 PIN1 UPS PIN2 PIN3 Ground PIN4 PIN5 UPS PIN6 PIN7 PIN8 UPS PIN9...

Page 29: ...24 1 2 UPS 3 4 2 8 EPO EPO Emergent Power Off EPO UPS EPO UPS UPS 1 2 3 4 UPS...

Page 30: ...25 2 9 UPS UPS UPS UPS O P I P...

Page 31: ...26 2 10 UPS UPS 10 LCD...

Page 32: ...27 3 LCD LED UPS 3 1 LED UPS UPS ESC ESC ESC C 6000FC LCD C 6000FCL LCD C 10000FC LCD C 10000FCL LCD...

Page 33: ...28 1 ON UPS 3 5 1 4 6 U P S 2 3 2 3 3 3 UPS LCD 2 1S XXXX XX XX...

Page 34: ...29 ECO 1 2 3 LCD 4 ECO ECO LCD ECO ECO 5 UPS 6 LCD 7 LCD...

Page 35: ...30 1S UPS 1 1 ESC 1 2 3 5 4 6 220 5V 60 0Hz K W 000 0 KVA 000 0 0 00 220 5V 60 0Hz 260 0V 95 0S 220 5V 45 5A 60 0Hz 3 4 C6000FC 3 0 1 7 100 220 0V 260V 7...

Page 36: ...31 1 2 1234 3 1 2 3 5 3 6 1 UPS 2 10S 10S 80 3 7...

Page 37: ...32 6 3 10S 4 UPS 5 100 220 0V 260V 1 2 3 1 2 1 99 1 3 UPS 1 2 ECO 3 4 5 6 UPS ECO ECO slewRate ECO...

Page 38: ...33 LED LED LED LED 1 LN E 2 LN E 3 LN E 4 5 6 Eeprom UPS 5 LED LED LED LED LED LED 3 8...

Page 39: ...34 1 10 LED 1 UPS 2 6 7 UPS 8 UPS 9 UPS 10 4 LED 4 1 C 6000F LED C 6000FL LED C 10000F LED C 10000FL LED 3C 10000F LED 3C 10000FL LED 3C 20000FL LED...

Page 40: ...35 12 2 6 13 2 10 Stanby Inverter 10 2 10 14 UPS 11 12 11 6 2...

Page 41: ...36 1 UPS UPS UPS UPS 4 2 UPS 12 UPS 1 UPS UPS...

Page 42: ...37 4 3 1 UPS UPS UPS 2 1 2 UPS UPS 4 1 UPS 2...

Page 43: ...38 4 4 1 6 UPS UPS 10 UPS 1 2 5 UPS UPS 1 4 UPS UPS 1 5 UPS UPS UPS UPS UPS 1 2 UPS UPS UPS 1 UPS UPS ON UPS OFF ON UPS UPS UPS UPS UPS UPS UPS...

Page 44: ...5 2 36 55 3 56 75 4 76 95 5 96 105 6 0 20 1 1 7 21 40 4 1 8 41 60 4 1 9 61 80 4 1 10 81 100 4 1 11 2 12 1 2 13 1 2 14 1 2 15 16 4 1 17 1 2 18 19 20 21 22 BUS 23 BUS 24 1 1 25 1 1 26 27 ID 28 1 2 6 29...

Page 45: ...40 5 UPS 1 2 15 25 3 UPS 3 4 5 3 5 6 35 UPS 36 1 1 37 1 2 3 38 1 1 39 ECO 1 1 40 Eeprom 1 1 3 41 PFC 42 43 44 45 RLY 46 SCR 47 48 49 50 NTC 51 52 CAN 53 54 4 1...

Page 46: ...41 1 2 3 4 5 6 7 8...

Page 47: ...42 9...

Page 48: ...be used for cleaning 7 In case of a fire hazard dry powder extinguisher should be used properly Using liquid fire extinguisher may result in electric shock hazard Electric Safety 1 Before electricity...

Page 49: ...s B Use insulated tools C Put on rubber shoes and gloves D Do not place metallic tools or similar metallic parts on the batteries E Switch off load connected to the batteries before dismantling batter...

Page 50: ...allel operation option 15 2 7 Communication card installation 22 2 8 EPO 23 2 9 Maintenance switch 24 2 10 Dustproof net option 24 Chapter 3 LCD Operation 25 3 1 Control panel 25 3 2 Start up 26 3 3 S...

Page 51: ...Do not place with sundries 1 This manual is designed for On Line series product as follows C 6000FC the standard model with internal battery and LCD C 6000FCL the long back up time model with external...

Page 52: ...r view 1 2 Front view 2 C 6000FC C 6000FCL C 10000FC C 10000FCL C 6000F C 6000FL C 10000F C 10000FL 3C 10000F 3C 10000FL 3C 20000FL C 6000FC C 6000FCL C 6000F C 6000FL C 10000FC C 10000FCL C 10000F C...

Page 53: ...Parallel card option cover EPO Emergency Power Off RS232 Battery connection socket Maintenance switch Cable clamp Intelligent slot Fan Input switch Terminal block cover 3C 10000F 3C 10000FL 3C 20000F...

Page 54: ...pass after 1 min 125 135 transfer to bypass after 30 seconds 135 transfer to bypass after 0 1 second Distortion THD 2 full linear load Battery the battery life reduce quickly under high temperature Ba...

Page 55: ...er 1 min 125 135 transfer to bypass after 30 seconds 135 transfer to bypass after 0 1 second Distortion THD 2 full linear load Battery the battery life reduce quickly under high temperature Backup tim...

Page 56: ...5 transfer to bypass after 1 min 125 135 transfer to bypass after 30 seconds 135 transfer to bypass after 0 1 second Distortion THD 2 full linear load Battery the battery life reduce quickly under hig...

Page 57: ...by 10 The output voltage is adjustable according to customer requirements 200 208 220 230 240 VAC Altitude m 1000 1500 2000 2500 3000 3500 4000 4500 5000 Coefficient 100 95 91 86 82 78 74 70 67 CAUTIO...

Page 58: ...future use 2 2 Wiring table CAUTION Choice of the diameter and cross section of conductors depend on the rated power of UPS Model C 6000F C 6000FL C 6000FC C 6000FCL C 10000F C 10000FL C 10000FC C 100...

Page 59: ...e appropriate position Model 3C 10000F 3C 10000FL 3C 20000FL Input G 10AWG or 22 mm2 hard wire 8AWG or 30 mm2 hard wire N 10AWG or 22 mm2 hard wire 6AWG or 38 mm2 hard wire L 10AWG or 22 mm2 hard wire...

Page 60: ...110V output Fig 3 6K 10K single phase input single phase 3 wires 220V 110V output Fig 1 6K 10K single phase input single phase 2 wires 220V output Fig 4 10K three phase input single phase 2 wires 220V...

Page 61: ...Fig 5 10K three phase input single phase 2 wires 110V output Fig 6 10K three phase input single phase 3 wires 220V 110V output Fig 7 20K three phase input single phase 2 wires 110V output BATTERY BAT...

Page 62: ...nd of battery to the corresponding terminal bay of UPS 4 Use multimeter DC Voltage to measure the voltage of positive and negtive batteries and check whether they are connected correctly Note non prof...

Page 63: ...et UPS and battery configurations are as follows UPS Cabinet C 6000FC C 6000FCL 12V 7AH 2 groups of 20 batteries 12V 26AH 1 group of 20 batteries 12V 40AH 1 group of 20 batteries C 6000F C 6000FL 12V...

Page 64: ...Connect the RS232 cable to the RS232 communication port of the UPS RS232 port settings are as follows Baud rate 2400bps String length 8bit End code 1bit Parity bit None The PIN configuration of comput...

Page 65: ...system can be configured with up to three UPS blocks Use the parallel cables to connect the parallel UPS with each other to realize power redundancy 2 Connection The parallel function is optional and...

Page 66: ...difference should be less than 20 When the lead from the output terminal of each set of UPS to the output patch board is longer than 20m wire difference should be less than 10 C The wiring connection...

Page 67: ...L C 10000FC C 10000FCL C 10000F C 10000FL 1 Single phase 2 wires 110V input switch input switch input switch output switch output switch output switch utility load 2 Single phase 2 wires 220V input sw...

Page 68: ...output switch utility load F Wiring connection diagram of parallel UPSs for 3C 10000F 3C 10000FL 1 Single phase 2 wires 110V G N R L1 N1 L2 N2 S T G N R L1 N1 L2 N2 S T G N R L1 N1 L2 N2 S T R S T L...

Page 69: ...N input switch input switch input switch output switch output switch output switch utility load 3 Single phase 3 wires 220V 110V G N R L1 N1 L2 N2 S T G N R L1 N1 L2 N2 S T G N R L1 N1 L2 N2 S T R S...

Page 70: ...es 110V output switch output switch output switch input switch input switch input switch load utility battery 1 battery 2 battery 3 2 Single phase 2 wires 220V output switch output switch output switc...

Page 71: ...ating guide to perform general operation 2 Power on Power on under main electrify the UPSs and then select COMMAND and confirm on the LCD of any set of UPS others are powered on at the same time and t...

Page 72: ...port AS400 card an optional accessory for intelligent slot The following is the pin assignment and description of DB 9 connector in AS400 card PIN Description PIN1 UPS Fail PIN2 Summary alarm PIN3 GND...

Page 73: ...an perform emergent power off when the UPS is under emergent condition Two methods to carry out cable connection as followed 1 2 close UPS perform Emergency power off 3 4 unused EPO Switch EPO Switch...

Page 74: ...nsure safe on line maintenance 2 10 Dustproof net option Dustproof net is used to protect the UPS from dust and it is necessary to install a dustproof net for the device at an environment with heavy d...

Page 75: ...or flashes in case of UPS fault and there are continuous or periodic beeps Keys Definition Description UP Scroll through lists on the same screen Down Scroll through lists on the same screen Confirm E...

Page 76: ...s 5 UPS is switching on 4 Press Enter to start up the UPS 6 Then the Switch off screen appears UPS SELFTESTING PLEASE WAIT LOADING ON PLEASE WAIT COMMAND CONFIGURATION HELP CONFIRM LOAD ON NO CANCEL Y...

Page 77: ...F ALL to enter the following screen Then press Enter to confirm In parallel mode you can select to load off single UPS alone or load off all units CONFIRM LOAD OFF ALL NO CANCEL YES CONFIRM 1 Switch o...

Page 78: ...E CONFIRM LOAD OFF ALONE NO CANCEL YES CONFIRM CONFIRM ECO DISABLE NO CANCEL YES CONFIRM Note the item STATE will display UPS power supply fault and alarm information by turns every 1S 1 The state scr...

Page 79: ...V VFREQ 60 0Hz BAT PARAMETER BAT VOLT 260 0V CAPACITY 95 BACKUP 0S OTHER PARAMETER MODEL C 6000FC VER 3 0 7 Press again to obtain the below information Note if you press now it will return to the stat...

Page 80: ...battery voltage low issue 2 Users can define the testing time or choose 10S COMMAND SELFTEST HELP SELFTEST TEST FOR 10S TEST AS SPEC TEST UNTIL 80 6 The following screen can be obtained if selftest fa...

Page 81: ...nge language between Chinese and English KEY To change user password OTHER 1 BUZZER 2 ECO 3 CONVER 4 PHASELOCK RATE 5 SERIAL 6 OTHER BUZZER To eliminate buzzer ECO Only applicable for single UPS CONVE...

Page 82: ...Bypass fault Battery overcharged one beep every 1 second Battery overcharged 2 Bypass mode Normal one beep every 2 mins Alarm one beep every 4 mins Line fault Alarm one beep every 1 second Battery not...

Page 83: ...inverter 10 Battery LED Whenever the orange battery LED is lit it shows that the load is powered by batteries It is applicable for the following models C 6000F the standard model with internal battery...

Page 84: ...tons 13 Function button silence press the button more than 2 seconds but less than 10 seconds to eliminate audible alarm in bypass mode and line mode press the button more than 10 seconds to eliminate...

Page 85: ...er to battery mode Line mode Indicator on off 4 2 Start up Turning on the UPS with AC Press ON button more than 1 second to start the UPS During the UPS performing self test all the Load Battery capac...

Page 86: ...2 seconds to silence the audible alarm 4 3 Shut down Press the OFF button more than 1 second to shut down the UPS The terminal still have live voltage via bypass and LED status is as follows In bypass...

Page 87: ...tinuously UPS overloaded or load fault Check the loads and remove non Critical loads Recalculate the load power and reduce the member of loads connected to the UPS Check whether the load is fault The...

Page 88: ...ypass mode Twice every 1s 15 Line abnormal None 16 Bypass abnormal Once every 4s 17 Overload in battery mode per alarm Twice every 1s 18 Overload in battery mode cut off the output Continuous beep 19...

Page 89: ...d write error Once every 1s totally 3 times 41 Recti er fault PFC fault Continuous beep 42 Negative power fault Continuous beep 43 Current unbalance Continuous beep 44 System power supply abnormal Con...

Page 90: ...recommended at the interval of 3 months 4 Replacement of accumulator batteries requires a match of same type and model with equal quantity and should follow the instructions given by battery supplier...

Page 91: ...er supply voltage or errors of power supply To damage caused by service including but not limited to movement overhauling repair modification and addition to other accessories performed by anyone who...

Page 92: ...INESS INVESTMENTS LOST GOODWILL OR LOST DATA OR DAMAGE OR FAILURE TO ANY OTHER EQUIPMENT THIS WARRANTY CARD SHALL CONSTITUTE OUR COMPANY S SOLE LIMIABLE AND PURCHASER S EXCLUSIVE REMEDY FOR THE PRODUC...

Page 93: ......

Page 94: ...EATON PHOENIXTEC MMPL CO LTD 614 08107 00 93 http www phoenixtec com tw 02 6600 6688 04 2328 1480 02 6606 8703 07 334 9119 0800 011912...

Reviews: