background image

Eaton

1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com

Eaton’s wireless business

www.eaton.com/wireless

Eaton is a registered trademark.

All other trademarks are property 
of their respective owners.

415U-2 wireless mesh networking I/O and gateway installation guide 

  
  

© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. IL032043EN 
April 2015

Instruction Leafl et 

IL032043EN

Effective July 2015

NOTE

All connections must be SELV <50 Vac and <120 Vdc.

The following illustrations show the ports on the 415U 2.

PWR

RF

232

485

LED Indicator 
Lights

I/O Connectors

RJ-45 Ethernet Port
(connects to hub or switch)

USB Port RS-232 Port

ETHERNET

USB

RS232

SUPPLY

+

-

GND BAT

SUP

SUP

+

B

A

-

+

Power supply wiring

The ground (GND) and “SUP –“ 
terminals are connected 
internally to the ground terminal.

Connect the screw terminal on 
the end plate to ground for surge 
protection.

Expanson I/O power and RS-485 serial connection

An on-board RS-485 
terminating resistor provides 
line attenuation for long runs.

Place terminating resisters 
at each end of the RS-485 
cable.

Confi guration switches

Use the DIP switches in the 
side access panel to select 
analog input voltage and 
current, external boot, and 
default configuration settings.

DIP

DESCRIPTION

1

AI3 current/voltage

2

AI3 current/voltage

3

AI4 current/voltage

4

AI4 current/voltage

5

Unused

6

Enables default configuration

Input and output connections

The digital input/output channels can be wired as inputs or outputs.

Digital input

Digital output

Transistor

Switch

Device

Voltage-free Contact

TTL CMOS

Output

D1

D3

D4

D5

D6

D7

D8

GND +24V

D2

DC Load

+

D1

D3

D4

D5

D6

D7

D8

GND +24V

D2

Differential current inputs (Al1, Al2)

Single-ended current input (Al3, Al4)

mA

Loop-Powered

Sensor

Exernally 

Powered

Sensor

Power Supply

D7

D8

GND +24V

AI1

+

AI1

_

AI2

+

AI2

_

AI3 AI4

AO1

+

AO2

+

GND +24V

mA

Loop-Powered

Sensor

Power Supply

Externally

Powered

Sensor

DIP Switch Setting

for Current IP

GND +24V

AI1

+

AI1

_

AI2

+

AI2

_

AI3 AI4

AO1

+

AO2

+

GND +24V

1     2     3    4     

5    6

ON

Analog output

Single-ended voltage input

AI

PLC

COM

AI1 AI1

_

AI2

+

AI2

_

AI3 AI4

AO1

+

AO2

+

GND +24V

0–25V 
Sensor

0–5 Vdc 

Sensor

+24V

AI1

+

AI1

_

AI2

+

AI2

_

AI3 AI4

AO1

+

AO2

+

GND +24V

V

V

DIP Switch Setting

for Voltage IP

ON

1     2     3    4     

5    6

ETHERNET

USB

RS232

B

A

-

+

115S-xx

115S-xx

RS-485

B

A

B

A

B

A

-

+

-

+

USB

RS232

SUPPLY

+

-

GND BAT

SUP

SUP

+

15-30 Vdc

Supply

3A Fuse 

Optional
10.8–15 Vdc
Lead Acid 
Battery

+

USB Host

Factory Boot 
Switch

%QPʙIWTCVKQP

Switches

Side 
Access 
Panel

All manuals and user guides at all-guides.com

Reviews: