background image

17

Instruction Book    

IB182217EN   October 2018   www.eaton.com

50 / 75 / 150 DHP [Cable or Hard Bus Application]

Ground and Test Device

SECTION 4:  DESCRIPTION AND OPERATION

The G&T is a draw out device that can be inserted into a circuit 

breaker cubicle in the same manner as the 50/150DHP Air Circuit 

Breaker and Vacuum Replacement Circuit Breaker. It can be ordered 

as a single terminal device or a double terminal ground and test 

device. Each terminal is isolated from each other and the ground bus 

connections by insulating barriers. The upper and lower terminals are 

accessible upon opening the respective fronthinged door. The ground 

connection is located in the lower section of the device.

m

 WARNING

IT IS MOST IMPORTANT THAT THE BUS OR LINE TERMINALS BE 

CORRECTLY IDENTIFIED FOR EACH COMPARTMENT BEFORE USING THIS 

DEVICE.

Type 50/150DHP manual Ground & Test devices are also available 

with either the upper or lower terminals only.

4.1 INSULATING BARRIERS

Insulating barriers are red pieces of GPO-3 glastic material used 

to isolate the primary terminals from each other and the ground 

connections. They are attached to the ground and test device frame 

using insulated hardware. Using other hardware than those provided 

will affect the insulating integrity of the ground and test device.

4.2 BUSHINGS AND DISCONNECTING CONTACT 

ASSEMBLIES

The upper and lower bushings, which are the primary circuit 

terminals of the ground and test device, consist of silver plated 

insulated conductors. Multiple finger type primary disconnecting 

contacts at the ends of the conductors provides means for 

connecting and disconnecting the G&T device to the bus terminals 

in the switchgear compartment. (Figure Set 3.3)

4.3 INTERLOCKS

The only interlocks associated with these Ground and Test devices 

are the Kirk

®

 Key interlocks located on the front of the device. (Figure 

Set 3.3) This protects the user from having both top and bottom 

hinged doors open at the same time. While either the top or bottom 

door is unlocked, the key is unable to be removed from the lock. To 

remove the key, close the appropriate door and turn the key. This 

will lock the door and the key will now be able to be removed and 

inserted into the other lock. This feature is not applicable for single 

terminal ground and test.

m

 NOTICE

ONLY ONE KEY WILL BE PROVIDED WITH EACH GROUND AND TEST 

DEVICE. THIS PREVENTS THE INTERLOCKING MECHANISM FROM BEING 

BYPASSED. IF A KEY IS LOST, CONTACT EATON FOR A REPLACEMENT. 

THIS FEATURE IS NOT APPLICABLE FOR SINGLE TERMINAL GROUND AND 

TEST.

m

 WARNING

INTERLOCKS ARE PROTECTIVE DEVICES FOR PERSONNEL AND 

EQUIPMENT. DO NOT BYPASS, MODIFY, OR MAKE INOPERABLE ANY 

INTERLOCKS. DOING SO COULD CAUSE DEATH, SERIOUS PERSONNEL 

INJURY, AND / OR PROPERTY DAMAGE.

4.4 GROUNDING CONTACTS

The grounding contact is an assembly of spring-loaded fingers, 

which ground the device by engaging the switchgear cell grounding 

bus when the G&T device is levered into the “connect” position. The 

ground contact is located at the rear of the device, on the truck, and 

visible from the back of the device when out of the cell. (Figure Set 

3.3)

Figure 4.2. G&T Device In Connect Position - Position “C”

4.5 BREAKER-CELL CODING PLATES

This is a combination of a notched plate in the cell and interference 

bars on the breaker, so that only appropriately rated breakers can be 

put into the cell (Figures 4.1 and 4.2). 

otee:

N

Code Plates provided on 1200A and 2000A devices only.

m

 WARNING

FOR 1200/2000A UNIVERSAL GROUND & TEST DEVICES A CODE PLATE HAS 

BEEN FACTORY INSTALLED TO MATCH THE RATING OF THE FACTORY-

INSTALLED PRIMARY DISCONNECTS. ENSURE THAT THE CORRECT 

PRIMARY DISCONNECTS AND CODE PLATES HAVE BEEN INSTALLED 

FOR THE CORRECT APPLICATION. TO CHANGE THE CODE PLATE SIMPLY 

REMOVE AND TURN AROUND SO THAT THE BAR IS POSITIONED AT THE 

TOP.

4.6 CELL POSITION DESCRIPTION

Position A: This is the withdrawn position. In the withdrawn position, 

the ground and test device is out of the cell. The racking handle is 

not required for this position.
Position B: As the G&T device is pushed into the cell, it will reach a 

mechanical stop. This is the “disconnect / test” position.
Position C: Continue rotating the racking handle until the rotating 

handle turns freely, and the G&T device stops moving. The device 

will have reached the “connect” position. (Figure 4.2) Remove the 

racking handle.

Figure 4.1. G&T Code Plates (1200A Shown)

5kV

15kV

Summary of Contents for 50 DHP

Page 1: ...182217EN 50 75 150 DHP Cable or Hard Bus Application Ground and Test Device Supersedes May 2016 Effective October 2018 150 DHP Ground and Test Device Hard Bus Type Device 150 DHP Ground and Test Devic...

Page 2: ...es office should be consulted Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between...

Page 3: ...PLATES 17 4 6 CELL POSITION DESCRIPTION 17 4 7 INSTALLATION OF GROUNDING BUS BARS 18 4 8 DEVICE AMPERAGE CONVERSION PROCEDURE 18 4 9 UNIVERSAL 1200A 2000A G T CONFIGURATION OPTIONAL 19 4 7 1 Changing...

Page 4: ...ng out tests m CAUTION BECAUSE OF THE UNIQUE APPLICATION AND VAST VARIETY OF SYSTEM USER REQUIREMENTS SPECIFIC SAFE OPERATING PROCEDURES FOR THE USE OF THIS DEVICE MUST BE DEVELOPED BY THE USER m WARN...

Page 5: ...aker Rated Continuous Current at 60 Hz Amps A B C D E F G H 50DHP 250 Dual 1200 2000 20 50 7 00 36 13 2 94 15 12 6 81 16 50 8 50 50DHP 350 Dual a 1200 2000 20 30 7 00 36 73 2 94 15 12 11 24 16 50 8 50...

Page 6: ...Bus Application Ground and Test Device Table 4 DHP Ground and Test Device Dimensions Hard Bus Application Design Breaker Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H 50...

Page 7: ...us Application Ground and Test Device Table 5 DHP Ground and Test Device Dimensions Hard Bus Application Design Breaker Type Existing Breaker Rated Continuous Current at 60 Hz Amps A B C D E F G H 150...

Page 8: ...st device from the enclosure before performing any maintenance Failure to do so could result in electrical shock leading to death severe personnel injury or property damage Do not leave the ground and...

Page 9: ...the original DHP air circuit breakers Use the racking handle originally provided to engage the racking shaft of the G T racking mechanism to move the device into and out of the circuit breaker compar...

Page 10: ...evice while lifting and moving Figure 3 2 a Front External View of 50DHP G T Device Figure 3 2 b Front External View of 150DHP G T Device 3 3 STORAGE If the ground and test device is to be placed in s...

Page 11: ...ton com 50 75 150 DHP Cable or Hard Bus Application Ground and Test Device Front External View 50DHP G T Shown 1 Kirk Key Interlocks 3 Ground Bus 5 Rail Latch 2 Door Latch 4 Levering Shaft Figure 3 3...

Page 12: ...150 DHP Cable or Hard Bus Application Ground and Test Device Figure 3 3 b Rear External View of DHP G T Device 1 1 2 6 5 4 3 Front External View 50DHP G T Shown 1 Primary Disconnects 3 Snubber Bolt 5...

Page 13: ...50 75 150 DHP Cable or Hard Bus Application Ground and Test Device 1 5 4 2 3 Figure 3 3 c Front External View of 50DHP 350 G T 3000A Device Front External View 150DHP G T Shown 1 Lifting Points 3 Grou...

Page 14: ...75 150 DHP Cable or Hard Bus Application Ground and Test Device 1 1 2 5 4 3 Figure 3 3 d Rear External View of 50DHP 350 G T 3000A Device Back External View 150DHP G T Shown 1 Primary Disconnects 3 Sn...

Page 15: ...ation Ground and Test Device Figure 3 3 e Front External View of 150DHP GT 500 1200A 2000A Device Front External View 1 Padlock Provision 3 Lifting Points 5 Levering Shaft 2 G T Storage Compartment 4...

Page 16: ...75 150 DHP Cable or Hard Bus Application Ground and Test Device Figure 3 3 f Rear External View of 150DHP GT 500 1200A 2000A Device Back External View 1 Primary Disconnect 3 Grounding Contact 5 Ground...

Page 17: ...ate door and turn the key This will lock the door and the key will now be able to be removed and inserted into the other lock This feature is not applicable for single terminal ground and test m NOTIC...

Page 18: ...nd and test device consists of cycloaliphatic bushings with silver plated copper conductor knobs Primary disconnecting contacts are attached to the knobs these primary disconnects are configured to en...

Page 19: ...tab ampere rating prior to inserting the G T device If the incorrect finger cluster is mounted on the G T device remove it and install the proper finger cluster 4 7 1 Changing 1200A Finger Clusters to...

Page 20: ...re 4 14 Figure 4 11 Finger Cluster Hardware Figure 4 13 Fitting 2000A Universal G T Finger Cluster Figure 4 14 2000A Universal G T Finger Cluster Removal Figure 4 12 Finger Cluster Hardware Thread the...

Page 21: ...THE SURFACE OF THE INSULATION OR WITHIN THE CELL BOTTLES FAILURE TO HEAD THIS WARNING CAN CAUSE DEATH SERIOUS PERSONNEL INJURY AND OR PROPERTY DAMAGE Orient the finger cluster with the stainless stee...

Page 22: ...in line with the location of the snubber bolts on each side of the ground and test device Figure 5 1 Step 2 Adjust the height of the top of the snubber bolt to be between 0 0 and 0 031 0 0 and 1 32 in...

Page 23: ...sh Continue cranking until the crank turns freely and the G T device stops moving The G T device should now be in the OPERATING or ENGAGED position 5 5 REMOVAL PROCEDURE To remove the G T device from...

Page 24: ...If a solvent is required to cut dirt used Stoddard s Solvent Eaton part number 55812CA or commercial equivalent Hardware Visually inspect all hardware Replace any damaged or missing hardware with par...

Page 25: ...to customer depending upon the service severity and continuity requirements Each customer should develop his own level based on operating experience 7 1 1 ORDERING INSTRUCTIONS 1 Always specify the gr...

Page 26: ...evard Cleveland OH 44122 United States Eaton com 2018 Eaton All Rights Reserved Printed in USA Publication No IB182217EN October 2018 Eaton is a registered trademark All trademarks are property of the...

Reviews: