Instruction Book
Effective: November 2017 Page 48
For more information visit:
www.Eaton.com
IB131016EN
Figure 5-25 Rugged Motor Operator Kit
Figure 5-26 Auxiliary Switch
Table 5.6 Motor Operator Ratings
Control
Voltages
Operational
Voltage Range
Running
Current
Inrush
Current
Power
Consumption
Charging
Time
24 Vdc
20-27
8 Amperes
400% of Running
250 VA
5 sec
48 Vdc
41-53
4 Amperes
400% of Running
250 VA
5 sec
110 Vdc
94 - 121
3 Amperes
400% of Running
250 VA
5 sec
125 Vdc
106 - 138
3 Amperes
400% of Running
250 VA
5 sec
220 Vdc
187 - 242
2 Amperes
400% of Running
250 VA
5 sec
250 Vdc
213 - 275
2 Amperes
400% of Running
250 VA
5 sec
110 Vac
94 - 121
3 Amperes
400% of Running
250 VA
5 sec
120 Vac
102- 132
3 Amperes
400% of Running
250 VA
5 sec
220 Vac
187 - 242
2 Amperes
400% of Running
250 VA
5 sec
240 Vac
204 - 264
2 Amperes
400% of Running
250 VA
5 sec
Table 5.7 Auxiliary Switch Contacts Interrupting Capacities
Continuous
Current
(amperes)
Control Circuit Voltage
120 Vac
240 Vac
24 Vdc
48 Vdc
125 Vdc
250 Vdc
Non-inductive Circuit Interrupting Capacity in Amperes
20
15 10 16
16
10
5
20
Inductive Circuit Interrupting Capacity in Amperes
15 10 16
16
10
5