Instruction Book
Effective: November 2017
Page 3
IB131016EN
For more information visit:
www.Eaton.com
Table 1.1 VCP-T and VCP-TR Ratings (ANSI C37. 04 and C37. 09) (continued from previous page)
Identification
Rated Values
Circuit
Breaker
Type
Voltage
Class
Insulation Level
Continuous
Current
Short Circuit `
Breaking
Current
Short Circuit
Making
Current
Mechanical
Endurance
C - O
Power
Frequency
Impulse
Withstand
kV rms
kV rms
kV Peak
Amperes
kA rms
kA Peak
Operations
150 VCP-T16
and
150 VCP-TR16
15 36 95
600
1200
1600
16 42
10000
10000
10000
150 VCP-T20
and
150 VCP-TR20
15 36 95
600
1200
1600
20 52
10000
10000
10000
150 VCP-T25
and
150 VCP-TR25
15 36 95
600
1200
1600
2000
2500
25 65
10000
10000
10000
10000
150 VCP-T32
and
150 VCP-TR32
15 36 95
600
1200
2000
2500
31.5 82
10000
10000
10000
10000
150 VCP-T40
and
150 VCP-TR40
15 36 95
600
1200
2000
2500
40 104
10000
10000
10000
10000
Use 15kV Breaker and Cassette when 95kV Impulse Withstand required
Also 2 Second Short Time Current Rating
1600A and 2500A available as fixed VCP-TR circuit breaker only
Tested for capacitor switching capabilities. “General Purpose” to ANSI C37: Cable charging = 25A. "Definite Purpose" to ANSI C37:
Back-to-back equals 250A and 1000A. Ratings of 250 and 1000A cover capacitor bank applications from 75 to 1000A.
Inrush current and frequency rating = 18 kApk at 2.4 kHz.