20
Instruction Book
IB182012EN March 2017 www.eaton.com
50DH-VR-50AXU / 50XU / 75U / 75ARU - 600 / 1200A
Replacement Circuit Breaker
Position J:
Once the racking mechanism is racked
counterclockwise until a mechanical stop is reached it is in the
disconnected position. The racking handle should be removed at this
point. The circuit breaker is ready to be removed from the switchgear
if desired.
Position K:
The circuit breaker is removed from the switchgear
by manually pulling on the handle located immediately below
the position mode indicator. The racking system is in the
“DISCONNECT” orientation. The circuit breaker is in a trip-free
status and in a non-operable state in the withdrawn position.
4.14 MISCELLANEOUS ITEMS
4.14.1 GROUNDING CONTACT
The grounding contact is an assembly of spring loaded fingers which
ground the circuit breaker frame (static ground) by engaging the
switchgear cell grounding bus when the circuit breaker is racked
into the cell. The ground contact is located at the rear of the circuit
breaker near the floor and visible from the back of the circuit breaker
when out of the cell.