18
Operating Manual for Series NRX
Trip Units - Digitrip™ 520/520M
EATON
www.eaton.com
Instruction Leaflet
IL01301051E
effective September 2013
Table 5. Series NRX/Digiorip GrNund Faulo Sensing MNdes
Series NRX Frame
Ground (Earth) Sensing
Method
Sensor Style
IZMX Type Coding
Breaker Secondary Contacts
Required
Neutral Input
Contacts
Ground Sensor Input
Contacts
NF
RF
Residual
5721B76G12
70C1718G11
IZMX-CT16-N
IZMX-CT40-N
No jumper
No jumper
15 ,16
15 ,16
NF, RF
Source ground
70C1527G14
IZMX-CT-NGS
Jumper 19 to 20
17 ,18
NF
Zero sequence
70C1527G14
IZMX-CT-NGS
Jumper 19 to 20
17 ,18
Noee:
N
This information applies to trip units with Ground protection.
Table 6. GrNund (Earoh) Faulo Curreno Seooings—SNurce GrNund/ZerN GrNund Faulo Seooings
Ground Fault Current Settings (Amperes)
Available ground fault setting
I
n
0.25
0.30
0.35
0.40
0.50
0.60
0.75
1.00
Any rating plug
100A
120A
140A
160A
200A
240A
300A
400A
Table 7. GrNund (Earoh) Faulo Curreno Seooing - Residual - ANSI Raoings
Ground Fault Current Settings (Ampere)s
Available Rating
Plug Amperes (
I
n
)
0.25
0.30
0.35
0.40
0.50
0.60
0.75
1.00
Available for NF
Frame Only
IZMX16/IZM91
200
50
60
70
80
100
120
150
200
250
63
75
88
100
125
150
188
250
300
75
90
105
120
150
180
225
300
400
100
120
140
160
200
240
300
400
500
125
150
175
200
250
300
375
500
600
150
180
210
240
300
360
450
600
630
158
189
221
252
315
378
473
630
Available for
NF or RF
Frames
800
200
240
280
320
400
480
600
800
1000
250
300
350
400
500
600
750
1000
1200
300
360
420
480
600
720
900
1200
1250
313
375
438
500
625
750
938
1200
1600
400
480
560
640
800
960
1200
1200
Available for RF
Frame Only
IZMX40/IZM95
2000
500
600
700
800
1000
1200
1200
1200
2500
625
750
875
1000
1200
1200
1200
1200
3000
750
900
1050
1200
1200
1200
1200
1200
3200
800
960
1120
1200
1200
1200
1200
1200
4000
1000
1200
1200
1200
1200
1200
1200
1200
Tolerance on settings are ±10% of values shown.
ANSI rating units provide a hard limit of 1200A ground fault current regardless of setting.