33
Instructional Leaflet
IL70C1037H05
Effective October 2009
Digitrip models 520, 520i; and 520M, 520Mi,
520MC, 520MCi trip units for use only in
Magnum and Magnum DS circuit breakers
eaton corporation
www.eaton.com
Figurt 47. Mainotnanct MNdt Wiring—Digiorip 520MC
Control
Voltage
e
L
Remote
Indicator
(BlueLight)
Remote Arcflash
Reduction Maintenance
System Switch
g
g
A12
B7
Alternate Customer
Wiring (partial)
a
b
A12
B7
A14
A15
A9
A10
B2
B1
Communication wiring to IR MINT,
BIM, MODBUS MINT or PowerNet
computer. This can activate
Maintenance Mode if desired.
Arcflash
Reduction
Maintenance
System Switch
a
f
Magnum Breaker (with MM wiring)
a
The Digitrip 520MC (Cat. #5ARMxxx) can locally be placed in Maintenance Mode via a two-position switch located on the trip unit. The function can also be armed via a remote switch as shown.
In addition, the function can also be activated via communications. A blue LED on the Digitrip verifies that Maintenance Mode is armed.
b
The recommended selector switch for this low voltage application is Eaton part number 10250T1333-2E, which includes a contact block rated for logic level and corrosive use.
c
The maximum length of this wiring to the remote Arcflash Reduction Maintenance System switch (or alternate relay contact) is 9.78 feet (3m). Use #20 AWG wire or larger.
d
Control voltage is 120 Vac or 230 Vac, or 24–48 Vdc or 125 Vdc. Check circuit breaker front cover for trip unit power requirements.
e
A remote stack light, annunciator panel, or other remote indication device can be connected to verify that the Digitrip is in Maintenance Mode.
f
Relay in GF Alarm/PS Module closes when Maintenance Mode is armed. Contact is rated 1A at 120 Vac or 0.5A at 230 Vac or 1A at 24–48 Vdc or 0.35A at 125 Vdc.
g
The Digitrip 520MC can also be placed remotely in its Maintenance Mode via a general purpose relay (ice cube type with logic level contacts) activated by a remote control switch.
A recommended type is IDEC Relay RY22. Choose voltage as desired.
d
c
c