Page 9
2. Presentation
2.4 LCD Description
Operation Status
Load/Equipment Status
Normal mode
100%
10min
100%
720W
800VA
Efficiency: ~98%
Battery Status
Efficiency and Load Group Information
As default, or after 5 minutes of inactivity, the LCD displays the screen saver.
The backlight LCD automatically dims after 10 minutes of inactivity. Press any button to restore the screen.
Note:
If any other indicator appears, see "Troubleshooting" on page 19.
UPS Operation Status
Possible Cause
Action
Standby mode
The UPS is OFF and waiting for a
start-up command from the user.
Connected equipment is not
powered until the [insert power
button symbol] button is pressed.
Normal mode
The UPS is operating normally.
The UPS is powering and protecting
the equipment.
In AVR mode
No beep
The UPS is operating normally but
the utility voltage is outside normal
mode thresholds.
The UPS is powering connected
equipment through the internal
Automatic Voltage Regulation (AVR)
device.
The equipment is still normally
protected.
On Battery
Battery LED is on
1 beep every 10 seconds
A utility failure has occurred and
the UPS is in Battery mode.
The UPS is supporting connected
equipment with battery power.
Prepare your equipment for
shutdown.
End of backup time
1 beep every 3 seconds
The UPS is in battery mode and
the battery is running low.
The warning is approximate, and
the actual time to shutdown may
vary significantly.
Depending on the UPS load,
the "Battery Low" warning may
occur before the battery reaches
20% capacity remaining.