Page 24
614-03898-00_EN
6. Appendices
6.1 Technical specifications
5P 2200
5P 3000
5P 1500 RT
5P 2200 RT
5P 3000 RT
Output Power @ 120 V
1440 VA
1440 W
1950 VA
1920 W
3000 VA
2700 W
Output Power capacity
@ 120 V
1500 VA
1500 W
2200 VA
1980 W
3000 VA
2700 W
Output Power @ 100 V
1200 VA
1200 W
1330 VA
1300 W
2400 VA
2160 W
AC Input power
l
Rated input voltage
l
Input voltage range
l
input frequency range
Single phase 100-125 V
80 to 162 V
(1)
47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system)
(2)
Output on battery power
l
Voltage
l
Frequency
100/120 V (-10/+6 %)
(3)
50/60 Hz ±0.1 Hz
Battery
(sealed lead acid,
maintenance free)
4 x 12 V
7.2 Ah
4 x 12 V
9 Ah
6 x 12 V
9 Ah
Environnement
l
Operating
temperature range
l
Storage
temperature range
l
Relative humidity
l
Noise level
0 to 40 °C
-15 to +50 °C
20 to 90 % (without condensation)
< 45 dBA
< 50 dBA
(1)
The high and low thresholds can be adjusted using UPS settings.
(2)
Up to 40 Hz in low -sensitivity mode (programmable using UPS settings).
(3)
Adjustable to 100 V.
For Models 5P 3000, 5P 3000 RT - "CAUTION - To reduce the risk of fire, connect only to a circuit provided
with 30 amperes maximum branch circuit overcurrent protection in accordance with the National Electric
Code, ANSI/NFPA 70".
For Models 5P 2200, 5P 2200 RT, 5P 1500 RT - "CAUTION - To reduce the risk of fire, connect only to a circuit
provided with 20 amperes maximum branch circuit overcurrent protection in accordance with the National
Electric Code, ANSI/NFPA 70".
This product is designed for IT power distribution system.
Filter
Transformer
"AVR"
Charger
Inverter
Battery
Summary of Contents for 5P 1500 RT