Page 26

620-00082-01-us (en)

6. Appendices

6.1 Technical specifications

Tower

5P 850G

5P 1550G

Rack

5P 850G R

5P 1550G R

Output Power @ 230 V

850 VA 

600 W

1550 VA 

1100 W

Output Power capacity
@ 208 V

765 VA 

540 W

1395 VA 

990 W

Output Power @ 200 V

765 VA 

540 W

1395 VA 

990 W

AC Input power

• 

 Rated input voltage

• 

 Input voltage range

• 

 Input frequency range

Single phase 200-240 V 

160 to 294 V 

(1)

 

47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system) 

(2)

Output on battery power

• 

Voltage

• 

Frequency

200/208/220/230/240 V (-10/+6 %) 

(3)

 

50/60 Hz ±0.1 Hz

Battery  
(sealed lead acid,  
maintenance free)

• 

Standard

Tower

2 x 12 V  

7 Ah

3 x 12 V 

9 Ah

Rack

4 x 6 V 

9 Ah

6 x 6 V 

9 Ah

Environment

• 

 Operating   

temperature range

• 

 Storage   

temperature range

• 

 Relative  humidity

• 

Noise level

0 to 35 °C

0 to 40 °C

-15 to +50 °C 

20 to 90 % (without condensation)

< 40 dBA

(1) 

The high and low thresholds can be adjusted using UPS settings.

(2)

 Up to 40 Hz in low -sensitivity mode (programmable using UPS settings).

(3) 

Adjustable to 200/208/220/230/240 V, must be set to the identical AC power source value.

When the appliance is used in EU area, use an external circuit breaker in front of line with rating 16 A,  

250 V which is IEC/EN 60898-1 standard compliant; 

When the appliance is used in America area, use an external circuit breaker in front of line with rating 20 A, 

250 V.

This product is designed for IT power distribution system.

Filter

Transformer 

"AVR"

Charger

Inverter

Battery

Summary of Contents for 5P 750

Page 1: ...00 5P 850G 5P 1550G Copyright 2012 EATON All rights reserved Service and support Call your local service representative 620 00082 01 us en 1U Rack models 5P 550 R 5P 750 R 5P 1000 R 5P 1500 R 5P 850G...

Page 2: ...Page 2 620 00082 01 us en...

Page 3: ...ed during installation and maintenance of the UPS and batteries The 5P models that are covered in this manual are intended for installation in an environment within 0 to 40 C free of conductive contam...

Page 4: ...der A protection circuit breaker must be installed upstream and be easily accessible The system can be disconnected from the AC power source by opening this circuit breaker Check that the indications...

Page 5: ...Rack 15 3 4 Installation of tower models 16 3 5 Installation of rack model for 2 post option 16 3 6 Installation of rack models 550 R 17 3 7 Installation of rack models 17 3 8 Installation of rack mod...

Page 6: ...ises over 50 of recycled cardboard Sacks and bags are made of polyethylene Packing materials are recyclable and bear the appropriate identification symbol 01 PET Materials Abbreviations Number in the...

Page 7: ...33 5P 850G 21 9 9 9 13 6 x 5 9 x 9 1 345 x 150 x 233 5P 1550G 35 2 15 9 17 5 x 5 9 x 9 1 445 x 150 x 233 Rack models H W D Description Weights lb kg Dimensions inch mm D x W x H 5P 550 R 17 80 8 08 14...

Page 8: ...rammable outlets for connection of equipment 6b Group 2 programmable outlets for connection of equipment 7 Attached 6 ft input power cord for AC power source 5 15P 8 LED indicating site wiring fault S...

Page 9: ...oup 6a Group 1 programmable outlets for connection of equipment 6b Group 2 programmable outlets for connection of equipment 7 Attached 6 ft input power cord for AC power source 5 15P 8 LED indicating...

Page 10: ...100 720W 800VA Efficiency 98 Escape Up Down Enter On Off button Rack models Normal mode 100 10min 100 720 W 800VA Efficiency 98 Alarm Indicator red On battery Indicator yellow Power On Indicator green...

Page 11: ...ser Equipment is not powered until button is pressed Normal mode The UPS is operating normally The UPS is powering and protecting the equipment In AVR mode No beep The UPS is operating normally but th...

Page 12: ...ttings The following table displays the options that can be changed by the user Description Available settings Default settings Local settings Language English Fran ais Deutsch Italiano Portugu s Espa...

Page 13: ...ically when mains recovers after a complete battery discharge Enable Energy saving Disable Enable If enabled UPS will shutdown after 5 min of back up time if no load is detected on the output Disable...

Page 14: ...1U Rack kit ears only for 550 R model 7 Front panel parts 8 2 connection cables for the protected equipments 850G and 1550G models 9 Cable locking systems 1 x 4 outlets 850G R models 1 x 6 outlets 15...

Page 15: ...ront panel B Connect the battery module never pull on the wires C Attach the front panel 3 3 Battery module connection Rack Caution Before starting the UPS please connect the internal battery Note A s...

Page 16: ...620 00082 01 us en 3 Installation 3 4 Installation of tower models 3 5 Installation of rack model for 2 post option 4 5 5 3 3 2 2 1 1 Use optional 1U 2 post rail kit Follow steps 1 to 5 for 2 post mo...

Page 17: ...ation of rack models Follow steps 1 to 4 for module mounting on the rails 1 1 2 2 3 3 4 4 The rails and necessary hardware are supplied by EATON 3 6 Installation of rack models 550 R Follow steps 1 to...

Page 18: ...Page 18 620 00082 01 us en 3 8 Installation of rack model for wall mounting 2 2 2 1 1 1 3 Installation...

Page 19: ...communication cards optional standard on the Network bundle models 3 It is not necessary to shutdown the UPS before installing a communication card 1 Remove the slot cover 3 secured by screws 2 Insert...

Page 20: ...See the Cold start setting in ON OFF Settings on page 13 To start the UPS on battery 1 Press the button on the UPS front panel until the UPS front panel display illuminates and shows a status of UPS...

Page 21: ...t down the UPS These functions are obtained by opening a contact connected between the appropriate pins of connector 4 on the rear panel of the UPS see figures below 4 Remote control connection and te...

Page 22: ...move some of the equipment from the UPS The UPS continues to operate but may shutdown if the load increases The alarm resets when the condition becomes inactive End of battery life The end of the batt...

Page 23: ...emoval on tower models This operation must be performed when the UPS is switched OFF A A Remove the front panel B B Disconnect the battery module by separating the town connectors never pull on the wi...

Page 24: ...Disconnect the battery module by separating the town connectors never pull on the wires D D Remove the metal protection cover in front of the battery two screws E E Pull the plastic tab to remove the...

Page 25: ...d lead acid maintenance free Standard Tower 2 x 12 V 7 Ah 2 x 12 V 9 Ah 3 x 12 V 9 Ah Rack 2 x 6 V 9 Ah 4 x 6 V 7 Ah 4 x 6 V 9 Ah 6 x 6 V 9 Ah Environment Operating temperature range Storage temperatu...

Page 26: ...V 9 Ah Rack 4 x 6 V 9 Ah 6 x 6 V 9 Ah Environment Operating temperature range Storage temperature range Relative humidity Noise level 0 to 35 C 0 to 40 C 15 to 50 C 20 to 90 without condensation 40 dB...

Page 27: ...is low and that the user must take action in light of the imminent break in the supply of power to the load Normal AC input The AC power line supplying the UPS under normal conditions Percent load Ra...

Page 28: ...Page 28 620 00082 01 us en...

Reviews: