Page 17
614-03797-00_EN
ENGLISH
3. Installation
3.6 Connection with a FlexPDU (Power Distribution Unit) module
(optional)
25
26
27
FlexPDU
5PX
1.
Connect the UPS powercord
10
to the AC-power source.
2.
Connect the input cord of the
FlexPDU
module
27
to one of
the UPS outlets
9
.
The cable and the connectors are
marked in red.
3.
Connect the equipment to the
outlets
25
and
26
on the
FlexPDU
module. These outlets differ,
depending on the version of the
FlexPDU
module.
3.7 Connection with a HotSwap MBP module
(optional)
The
HotSwap
MBP module makes it possible to service or even replace the UPS without affecting the connected
loads (
HotSwap
function).
UPS ON
OK
to
switch
No
rm
al
UPS OU
T
UPS IN
A
C
PO
WE
R
By
Pa
ss
HotSwap MBP
5PX
28
29 30 31
34
32
33
1.
Connect the input socket
34
on
the
HotSwap MBP
module to the
AC-power source.
2.
Connect the UPS input socket
10
to the "UPS Input"
33
of the
HotSwap MBP
module.
This cord and the receptacle are
marked blue.
3.
Connect the UPS outlet
7
to the
"UPS Output"
32
of the
HotSwap
MBP
module.
This cord and the outlet are
marked red.
4.
Connect the equipment to the
outlets
28
on the
HotSwap MBP
module.
These outlets differ, depending on
the version of the
HotSwap MBP
module.
Caution: Do not use UPS outlets
8
and
9
to supply equipment because
use of switch
31
on the HotSwap
MBP module would cut supply to
the equipment.