34003906EN/AE - 3
The
Network Management Card & Modbus/Jbus
(66103) is recommended for central UPSs
protecting entire networks or for UPS units backing up critical loads. With the card installed, the UPS
has its own IP address and uses the local computer capabilities to:
●
Supply web pages (http or https (SSL)) with information on status conditions and measurements/
settings/alarms,
●
Integrate an SNMP-based NMS such as HP OpenView, IBM Tivoli Netview and Computer Associates
Unicenter,
●
Communicate with shutdown modules installed on the protected servers (Network Shutdown
Module),
●
Send e-mail and SMS messages,
●
Control the ON/OFF function of the UPS and the outlets,
●
Monitor the Environment Sensor (optional, cat. no. 66846).
●
One
Network Management Card & Modbus/Jbus
(66103)
●
One serial cable for configuration (34003918),
●
One installation manual (34003906).
The Network Management Card & Modbus/Jbus (66103) is compatible with the Pulsar range UPSs
available since 2006.Note.
●
If the technical level of the UPS is lower than that indicated in the table, contact EATON.
UNPACKING AND CHECKS
CHECK ON UPS VERSION
Important. Before installing the card, check that the UPS technical level (NT) is at least
equal to that indicated in the table below.
UPS
Type
Technical level (NT)
Pulsar
700/1000/1500
02
Pulsar M
2200/3000
03
Pulsar MX
4000/5000/10000
04
Pulsar MX Frame
15/20 kVA
01