14
5.3 Connection to mains and loads (700 - 3000 VA)
The following Input and Output cables come supplied with all models
700 VA, 1000 VA,
(option)- IEC 320 10 A (Input cable)
1500 VA, 2000 VA
Two IEC-IEC 320 10 A (Load cable)
3000 VA
(option)-IEC 320 16 A (Input cable)
Two IEC-IEC 320 10 A (Load cable)
z
Ensure that the UPS is disconnected from mains and loads while connecting the External
Battery Cabinets, if needed.
z
Use the battery cable that comes with the External Battery Cabinet to connect the
External Battery Cabinet to the UPS. Connect a second battery cabinet to the first one
with the cable provided if more than one is to be installed.
z
Be aware of UPS parameters and changing the Battery pack quantity when using the
external battery cabinets (see chapter 7.2)
z
Connect the Input cable to the UPS and connect the other end to a grounded outlet. The
batteries will automatically charge when connected to the mains. Please realize that
although you may start using the UPS immediately, maximum back-up time will still not
be available, so it is recommended to charge the batteries for a minimum of 8 hours
before use.
z
If unit instantly shows a “Site Wiring Fault”, rotate the connector (Schuko) (see chapter
7.4).
z
After charging, connect the loads to the UPS (see the example in fig 3).
z
Do not connect any devices that have the possibility of overloading the UPS or drawing
half-wave rectified current, such as hair dryers or vacuum cleaners.
z
Should computer or alarm connections be used, use connections according to chapter 6
of the manual provided with that option. The connections can be referred to on the rear
panel.
z
The installation is now complete
.
15
Fig. 3
Example of Installation of Plug & Play products
5.4 Default settings at the factory
On the LCD display you will find several of the UPS parameters to select.
Default settings are as follows:
Settings Selection
Factory
default
100/110/115/120/127
Vac
120V (FOR LV series)
Output Voltage Setting
208/220/230/240 Vac 230V (FOR HV series)
Input/Bypass Voltage
±10%
+10/-15%
+15/-20%
+10/-15%
Input/Frequency
±2%
±5%
±7%
±5%
HE Mode Setting
On/Off
Off
Free Run Mode
On/Off
On
Bypass Enable/Disable at free run mode
Disable/Enable
Disable
Alarm silence
On/Off
Off
Site wiring alarm
Enable/Disable
Disable
External Battery pack setting
0, 1, 2
0
You may change default settings, but we recommend that this is done after installation and
before starting up loads. Read UPS configurations in chapter 7.2 for more information.