14 

5.3 Connection to mains and loads (700 - 3000 VA) 

The following Input and Output cables come supplied with all models 

700 VA, 1000 VA,   

(option)- IEC 320 10 A (Input cable) 

1500 VA, 2000 VA 

Two IEC-IEC 320 10 A (Load cable) 

3000 VA   

(option)-IEC 320 16 A (Input cable) 

 

Two IEC-IEC 320 10 A (Load cable) 

z

 

Ensure that the UPS is disconnected from mains and loads while connecting the External 
Battery Cabinets, if needed. 

z

 

Use the battery cable that comes with the External Battery Cabinet to connect the 
External Battery Cabinet to the UPS. Connect a second battery cabinet to the first one 
with the cable provided if more than one is to be installed. 

z

 

Be aware of UPS parameters and changing the Battery pack quantity when using the 
external battery cabinets (see chapter 7.2) 

z

 

Connect the Input cable to the UPS and connect the other end to a grounded outlet. The 
batteries will automatically charge when connected to the mains. Please realize that 
although you may start using the UPS immediately, maximum back-up time will still not 
be available, so it is recommended to charge the batteries for a minimum of 8 hours 
before use. 

z

 

If unit instantly shows a “Site Wiring Fault”, rotate the connector (Schuko) (see chapter 
7.4). 

z

 

After charging, connect the loads to the UPS (see the example in fig 3). 

z

 

Do not connect any devices that have the possibility of overloading the UPS or drawing 
half-wave rectified current, such as hair dryers or vacuum cleaners. 

z

 

Should computer or alarm connections be used, use connections according to chapter 6 
of the manual provided with that option. The connections can be referred to on the rear 
panel. 

z

 

The installation is now complete 

.

 

15

 

 

 

 

 

 

 

 

Fig. 3 

Example of Installation of Plug & Play products 

5.4 Default settings at the factory 

On the LCD display you will find several of the UPS parameters to select. 
Default settings are as follows: 

Settings Selection 

Factory 

default 

100/110/115/120/127 
Vac 

120V (FOR LV series) 

Output Voltage Setting 

208/220/230/240 Vac 230V (FOR HV series) 

 

Input/Bypass Voltage 

±10% 

+10/-15% 

+15/-20% 

+10/-15% 

 

Input/Frequency 

±2% 

±5% 

±7% 

±5% 

HE Mode Setting 

On/Off 

Off 

Free Run Mode 

On/Off 

On 

Bypass Enable/Disable at free run mode

Disable/Enable 

Disable 

Alarm silence 

On/Off 

Off 

Site wiring alarm 

Enable/Disable 

Disable 

External Battery pack setting 

0, 1, 2 

You may change default settings, but we recommend that this is done after installation and 
before starting up loads. Read UPS configurations in chapter 7.2 for more information.

Summary of Contents for 700VA

Page 1: ...easures z Place the receiving antenna in a separate location or orientation z Ensure a greater distance is achieved between the receiver and the equipment z Ensure that your equipment is connected to...

Page 2: ...isk of electric shock do not remove cover No user serviceable parts inside Refer servicing to qualified service personnel CAUTION Non isolated Battery supply Risk of electric shock battery circuit is...

Page 3: ...ly detailed requirements of the UPS units are described herein and installation must be carried out in accordance with this manual Electrical installations must also carefully follow local legislation...

Page 4: ...eports any problems on the LCD display An advanced battery management system always monitors the conditions of the batteries sends any forewarnings if replacement is needed Otherwise every 30 days of...

Page 5: ...operations are to be performed exactly as instructed in this manual The greatest care possible must be taken for any of these operations and any change thereof may prove very hazardous to the operato...

Page 6: ...he following illustration Vertical Installation Wall mounted installation 7 Installation with accessories of Rack mounted types Please install the types of units according to the following illustratio...

Page 7: ...8 Installation with accessories of Stack types Please install the types of units according to the following illustration Stack installation 9 5 2 Rear panel views 700 1 5KVA REAR PANEL...

Page 8: ...10 2K 3KVA REAR PANEL 11 RM 1U 700 1KVA Rear Panel...

Page 9: ...12 RM 2U 700 1K 1 5KVA Rear Panel 13 RM 2U 2K 3KVA Rear Panel...

Page 10: ...instantly shows a Site Wiring Fault rotate the connector Schuko see chapter 7 4 z After charging connect the loads to the UPS see the example in fig 3 z Do not connect any devices that have the possi...

Page 11: ...ctions 2 TxD Output TxD Output 3 RxD Input RxD Inverter Off Input 5 Common Common 6 Output Ac Fail Output 8 Output Low Battery Output 9 Output 12 VDC Power Caution Max rated values 12Vdc 17 USB port o...

Page 12: ...off the UPS 2 is a Enter button Use this button to check content of UPS and the method is listed below a Push the button at least 2 seconds to check content of UPS Each content can be displayed by pr...

Page 13: ...URE xxC Shows approximate ambient temperature BAT PACK NUM x Shows External Battery Pack Number RATING xxxxVA Shows UPS Rating CPU VERSION xx x Shows CPU Version 21 UPS configurations 1 Various settin...

Page 14: ...32 communication RS232 Control Set RS232 communication enable or disable Enable Disable Enable 23 Manual test of the UPS Manual UPS or Manual Battery tests can be conducted from the UPS configuration...

Page 15: ...er second High internal DC bus Voltage Turn off protected loads Turn off UPS and call your local dealer Site wiring Fault 1 Beep per second Voltage detected Between Neutral and Ground UPS mains connec...

Page 16: ...144 VAC Frequency 50 60 Hz Auto selection Frequency window from mains 45 65 Hz Synchronization window 3Hz Input current 700 VA 5 8A 1000 VA 8 2A 1500 VA 12 4A 2000 VA 16 5A 3000 VA 24 7A Input Power...

Page 17: ...attery mode 700 1000 VA 50 db normal and battery mode 1500 3000 VA 29 STANDARDS Safety EN50091 1 1 Emissions EN50091 2 Immunity EN50091 2 B 700 1500VA A 2K 3KVA HV Model OUTPUT POWER 700VA 490 W 1000V...

Page 18: ...o 90 3 hours to 90 3 hours to 90 Dimensions W x D x H mm 152 x 420 x 238 152 x 420 x 238 152 x 420 x 238 225 x 425 x 360 225 x 425 x 360 Weight kg 13 5 16 2 17 31 6 33 31 19 Rack mount Model 2U OUTPUT...

Page 19: ...20 x 238 152 x 420 x 238 225 x 425 x 360 225 x 425 x 360 Dimensions W x D x H mm RM2U 428 x 425 x 84 428 x 425 x 84 428 x 425 x 84 428 x 610 x 84 428 x 610 x 84 Tower 21 21 21 42 42 Weight Kg RM2U 22...

Reviews: