background image

 

20 

Status of the UPS, measurements and alarms are all indicated on the LCD screen. 

 

 

 

 

 

 

Figure 6. 

Control panel 

Normal display 

The UPS status is shown in normal display mode. From here you have a choice to go to UPS 
meters display and the Setting display by pushing the button. 

UPS meters display 

Various measurements are available through the UPS meters display; pressing 
the button will scroll through the following meters: 

LCD message 

Description 

O/P VOLT= xxx, xV 

Shows Output AC voltage 

O/P FREQ= xx, x Hz 

Shows Output Frequency 

I/P VOL T= xxx, xV 

Shows Input AC voltage 

I/P FREQ= xx, x Hz 

Shows Input Frequency 

BAT VOLT= xx,xV 

Shows Battery Voltage 

O/P LOAD%= xx% 

Shows Load % of max load 

O/P W= xW 

Shows Output Watts 

O/P VA= xVA 

Shows Output VA 

O/P CURR= xA 

Shows Output Current 

BACKUP TIME= xx min Shows Estimated Backup time in minutes 

BAT CHARG= xx% 

Shows approximate percentage of Battery capacity 

TEMPERATURE= xxC 

Shows approximate ambient temperature 

BAT PACK NUM= x 

Shows External Battery Pack Number 

RATING = xxxxVA 

Shows UPS Rating 

CPU VERSION xx.x 

Shows CPU Version 

 

 

 

21

UPS configurations 

1.

 

Various settings that have been chosen are shown in the UPS setting display. 

2.

 

To enter configuration mode, press the        button for one second. The first 
configuration parameter will be shown on the LCD display. 

3.

 

Press the        button to scroll through the parameters. 

4.

 

Press the        button to select the parameter. 

5.

 

Press the        button to scroll through the options for the selected parameter; Press   
the    button to select the option. 

You may be prompted to save the selection, if so press the        button to either confirm 
or save your selection. Other options are saved and started automatically. See the table 
below for further details. 

6.

 

If no buttons are pressed (or user inactivity) for ten seconds, the UPS shall exit the 
configuration mode and return to normal mode displaying Line mode. 

Caution! 

The factory default settings do not necessarily have to be changed, although 
you are free to tailor the UPS to your specific needs. 

 

 

 

 

Summary of Contents for 700VA

Page 1: ...easures z Place the receiving antenna in a separate location or orientation z Ensure a greater distance is achieved between the receiver and the equipment z Ensure that your equipment is connected to...

Page 2: ...isk of electric shock do not remove cover No user serviceable parts inside Refer servicing to qualified service personnel CAUTION Non isolated Battery supply Risk of electric shock battery circuit is...

Page 3: ...ly detailed requirements of the UPS units are described herein and installation must be carried out in accordance with this manual Electrical installations must also carefully follow local legislation...

Page 4: ...eports any problems on the LCD display An advanced battery management system always monitors the conditions of the batteries sends any forewarnings if replacement is needed Otherwise every 30 days of...

Page 5: ...operations are to be performed exactly as instructed in this manual The greatest care possible must be taken for any of these operations and any change thereof may prove very hazardous to the operato...

Page 6: ...he following illustration Vertical Installation Wall mounted installation 7 Installation with accessories of Rack mounted types Please install the types of units according to the following illustratio...

Page 7: ...8 Installation with accessories of Stack types Please install the types of units according to the following illustration Stack installation 9 5 2 Rear panel views 700 1 5KVA REAR PANEL...

Page 8: ...10 2K 3KVA REAR PANEL 11 RM 1U 700 1KVA Rear Panel...

Page 9: ...12 RM 2U 700 1K 1 5KVA Rear Panel 13 RM 2U 2K 3KVA Rear Panel...

Page 10: ...instantly shows a Site Wiring Fault rotate the connector Schuko see chapter 7 4 z After charging connect the loads to the UPS see the example in fig 3 z Do not connect any devices that have the possi...

Page 11: ...ctions 2 TxD Output TxD Output 3 RxD Input RxD Inverter Off Input 5 Common Common 6 Output Ac Fail Output 8 Output Low Battery Output 9 Output 12 VDC Power Caution Max rated values 12Vdc 17 USB port o...

Page 12: ...off the UPS 2 is a Enter button Use this button to check content of UPS and the method is listed below a Push the button at least 2 seconds to check content of UPS Each content can be displayed by pr...

Page 13: ...URE xxC Shows approximate ambient temperature BAT PACK NUM x Shows External Battery Pack Number RATING xxxxVA Shows UPS Rating CPU VERSION xx x Shows CPU Version 21 UPS configurations 1 Various settin...

Page 14: ...32 communication RS232 Control Set RS232 communication enable or disable Enable Disable Enable 23 Manual test of the UPS Manual UPS or Manual Battery tests can be conducted from the UPS configuration...

Page 15: ...er second High internal DC bus Voltage Turn off protected loads Turn off UPS and call your local dealer Site wiring Fault 1 Beep per second Voltage detected Between Neutral and Ground UPS mains connec...

Page 16: ...144 VAC Frequency 50 60 Hz Auto selection Frequency window from mains 45 65 Hz Synchronization window 3Hz Input current 700 VA 5 8A 1000 VA 8 2A 1500 VA 12 4A 2000 VA 16 5A 3000 VA 24 7A Input Power...

Page 17: ...attery mode 700 1000 VA 50 db normal and battery mode 1500 3000 VA 29 STANDARDS Safety EN50091 1 1 Emissions EN50091 2 Immunity EN50091 2 B 700 1500VA A 2K 3KVA HV Model OUTPUT POWER 700VA 490 W 1000V...

Page 18: ...o 90 3 hours to 90 3 hours to 90 Dimensions W x D x H mm 152 x 420 x 238 152 x 420 x 238 152 x 420 x 238 225 x 425 x 360 225 x 425 x 360 Weight kg 13 5 16 2 17 31 6 33 31 19 Rack mount Model 2U OUTPUT...

Page 19: ...20 x 238 152 x 420 x 238 225 x 425 x 360 225 x 425 x 360 Dimensions W x D x H mm RM2U 428 x 425 x 84 428 x 425 x 84 428 x 425 x 84 428 x 610 x 84 428 x 610 x 84 Tower 21 21 21 42 42 Weight Kg RM2U 22...

Reviews: