22 

 

Settings 

LCD 
display 

Explanation Selection 

Factory 
default 

208/220/230/240 V 

230V 

Output Volt.Setting 

O/P V 
Setting 

Select Nominal Voltage 

100/110/115/120/127 V 

120V 

Input/Frequency I/P 

Setting

Select input frequency 
range when UPS goes into 
free run mode 

±2% 
±5% 
±7% 

±5% 

Input/Bypass 
Voltage 

I/P Bypass 
Set 

Select Input Voltage range 
when bypass is available 

±10% 
+10/-15% 
+15/-20% 

+10/-15%

Free Run Mode 

Free Run 
Set

 

Select if UPS can run in 
Free run mode 
(unsynchronized) 

ON/OFF ON 

Bypass 
Enable/Disable at 
Free run mode 

Bypass 
disable 

If Enable is chosen, the 
UPS can go to bypass when 
unsynchronized. 

Disable/Enable Disable 

He mode Setting 

HE Mode 
Set 

Select if UPS runs in high 
efficiency mode 

ON/OFF OFF 

Force Manual 
Bypass 

Manual 
bypass 

Permanently force UPS to 
bypass. For service only.** 

ON/OFF

 

OFF 

Management of 
Load groups 

Outlet 
Setting 

You can put the two load 
groups on and off form 
front panel 

1 ON & 2 ON 
1 OFF & 2 ON 
1OFF & 2 OFF 
1 ON & 2 OFF

 

Both load 
segments 
ON 

Do Battery Test 

Battery Test

Detect battery is normal or 
not. 

 

 

Silence Function 

Silence Set

Enable or disable silence 
function 

ON/OFF

 

OFF 

Number of 
External battery 
Packs 

Bat Cabinet 
Set 

This setting is needed 
For UPS to predict 
Backup time 

0 (only internal batteries)
1(one external cabinet) 
2 (two external cabinets)

 

Site wiring alarm 

Sit Fault Set

You can enable or disable 
the site wiring alarm 

Enable /Disable

 

Disable 

Select Language 

Language 

Select load language 

English, German, French, 
Spanish, Italian. 

English 

Set Generator Mode  Generator 

Set unit in generator mode. 
*** 

ON/OFF OFF 

Set RS232 
communication 

RS232 
Control 

Set RS232 communication 
enable or disable 

Enable/Disable Enable 

 

 

23

Manual test of the UPS 

Manual UPS or Manual Battery tests can be conducted from the UPS configuration as well 
and are functional even when the UPS is not charging the battery. 

Manual Battery test:  Scroll the parameters until Manual Bat test displays on the LCD. 

Press the    button twice. 

 

**) Note: In order for the UPS and power management software to operate normally, 
Manual Bypass should always be set to OFF as the load will not be protected by the unit 
when Manual Bypass is ON. This is aimed for operating an external maintenance bypass 
switch. 

***) Note: You should turn UPS off and keep the AC power before you use “Generator” 
function. (even you want to select “\Generator\OFF” to back to normal mode). 

 

7.4 Interpreting UPS messages 

Troubleshooting procedures described here give simple instructions in determining UPS 
malfunctions. 

Start the troubleshooting procedure if you witness any alarm indication on the control panel. 

Alarm indicators 

The UPS gives the following audible alarms: 

z

 

If UPS is on battery and the ON BATTERY LED is on, UPS will beep every 5 seconds. 

z

 

If the battery capacity is low and the ON BATTERY LED is flashing, the UPS will beep 
twice every 5 seconds. 

z

 

If UPS is on bypass and the BYPASSED LED is on, UPS will no beep. 

z

 

If UPS has an internal fault and the ALARM LED is on, the UPS will give a constant 
audible alarm displaying the cause on the LCD display. 

Silencing an alarm 

By pressing any of the three buttons on the front panel, the alarm can be turned off, except 
when the battery is low, which will cause the alarm to resound. 

On the LCD display, you can also choose silent alarm mode which will not warn you of any 
malfunction audibly. 

Summary of Contents for 700VA

Page 1: ...easures z Place the receiving antenna in a separate location or orientation z Ensure a greater distance is achieved between the receiver and the equipment z Ensure that your equipment is connected to...

Page 2: ...isk of electric shock do not remove cover No user serviceable parts inside Refer servicing to qualified service personnel CAUTION Non isolated Battery supply Risk of electric shock battery circuit is...

Page 3: ...ly detailed requirements of the UPS units are described herein and installation must be carried out in accordance with this manual Electrical installations must also carefully follow local legislation...

Page 4: ...eports any problems on the LCD display An advanced battery management system always monitors the conditions of the batteries sends any forewarnings if replacement is needed Otherwise every 30 days of...

Page 5: ...operations are to be performed exactly as instructed in this manual The greatest care possible must be taken for any of these operations and any change thereof may prove very hazardous to the operato...

Page 6: ...he following illustration Vertical Installation Wall mounted installation 7 Installation with accessories of Rack mounted types Please install the types of units according to the following illustratio...

Page 7: ...8 Installation with accessories of Stack types Please install the types of units according to the following illustration Stack installation 9 5 2 Rear panel views 700 1 5KVA REAR PANEL...

Page 8: ...10 2K 3KVA REAR PANEL 11 RM 1U 700 1KVA Rear Panel...

Page 9: ...12 RM 2U 700 1K 1 5KVA Rear Panel 13 RM 2U 2K 3KVA Rear Panel...

Page 10: ...instantly shows a Site Wiring Fault rotate the connector Schuko see chapter 7 4 z After charging connect the loads to the UPS see the example in fig 3 z Do not connect any devices that have the possi...

Page 11: ...ctions 2 TxD Output TxD Output 3 RxD Input RxD Inverter Off Input 5 Common Common 6 Output Ac Fail Output 8 Output Low Battery Output 9 Output 12 VDC Power Caution Max rated values 12Vdc 17 USB port o...

Page 12: ...off the UPS 2 is a Enter button Use this button to check content of UPS and the method is listed below a Push the button at least 2 seconds to check content of UPS Each content can be displayed by pr...

Page 13: ...URE xxC Shows approximate ambient temperature BAT PACK NUM x Shows External Battery Pack Number RATING xxxxVA Shows UPS Rating CPU VERSION xx x Shows CPU Version 21 UPS configurations 1 Various settin...

Page 14: ...32 communication RS232 Control Set RS232 communication enable or disable Enable Disable Enable 23 Manual test of the UPS Manual UPS or Manual Battery tests can be conducted from the UPS configuration...

Page 15: ...er second High internal DC bus Voltage Turn off protected loads Turn off UPS and call your local dealer Site wiring Fault 1 Beep per second Voltage detected Between Neutral and Ground UPS mains connec...

Page 16: ...144 VAC Frequency 50 60 Hz Auto selection Frequency window from mains 45 65 Hz Synchronization window 3Hz Input current 700 VA 5 8A 1000 VA 8 2A 1500 VA 12 4A 2000 VA 16 5A 3000 VA 24 7A Input Power...

Page 17: ...attery mode 700 1000 VA 50 db normal and battery mode 1500 3000 VA 29 STANDARDS Safety EN50091 1 1 Emissions EN50091 2 Immunity EN50091 2 B 700 1500VA A 2K 3KVA HV Model OUTPUT POWER 700VA 490 W 1000V...

Page 18: ...o 90 3 hours to 90 3 hours to 90 Dimensions W x D x H mm 152 x 420 x 238 152 x 420 x 238 152 x 420 x 238 225 x 425 x 360 225 x 425 x 360 Weight kg 13 5 16 2 17 31 6 33 31 19 Rack mount Model 2U OUTPUT...

Page 19: ...20 x 238 152 x 420 x 238 225 x 425 x 360 225 x 425 x 360 Dimensions W x D x H mm RM2U 428 x 425 x 84 428 x 425 x 84 428 x 425 x 84 428 x 610 x 84 428 x 610 x 84 Tower 21 21 21 42 42 Weight Kg RM2U 22...

Reviews: