The following is a step-by-step tutorial for replacing the batteries:
1.
The front panel of the UPS can be removed by pushing where the arrows indicate in the
pictures above. Next, unscrew the screws and remove the metal battery cover.
2.
Remove the battery cartridge from the UPS. The voltage in all models will be less than
48Vdc once the battery is disconnected from the UPS.
3.
Replace the batteries.
4.
Push the cartridge with the new batteries back into the UPS.
5.
Reinstall the metal plate and the front panel.
27
10.1 Power Range 700-3000 VA (LV)
GENERAL
Rated power
700VA, 1000 VA, 1500 VA, 2000 VA, 3000 VA at p.f 0.7
Technology
On-line, double conversion topology with automatic bypass
INPUT
Phase:
Single phase with ground
Bypass Voltage
96-138 VAC (user selectable)
Input Voltage range:
60/70/80VAC-144 VAC
Frequency:
50/60 Hz. Auto selection
Frequency window from mains
45-65 Hz
Synchronization window
± 3Hz.
Input current
700 VA 5.8A, 1000 VA 8.2A, 1500 VA 12.4A, 2000 VA 16.5A
3000 VA 24.7A
Input Power factor:
0.97
OUTPUT
Output Voltage:
100/110/115/120/127 VAC, selectable from LCD panel
Voltage regulation:
± 2%
Voltage distortion:
< 5% THD at full non-linear load, < 3% THD at full linear load
Frequency regulation
± 0.25 Hz (battery or free running mode)
* 60V at 40% load, 70V at 70%, 80V at 100%.
10.2 Power Range 700-3000 VA (HV)
GENERAL
Rated power
700VA, 1000 VA, 1500 VA, 2000 VA, 3000 VA at p.f 0.7
Technology
On-line, double conversion topology with automatic bypass
INPUT
Phase
Single phase with ground
Bypass Voltage:
184-265 VAC (user selectable)
Input Voltage range:
120/140/160 VAC-276 VAC
Frequency:
50/60 Hz. Auto selection
Frequency window from mains
45-65 Hz
Synchronization window
± 2.5Hz.
Input current
700 VA 3A, 1000 VA 4A, 1500 VA 5.7A, 2000 VA 7.7A, 3000 VA
12A
Input Power factor:
0.97