background image

Contents

Description Page

1.0  General Description   . . . . . . . . . . . . . . . . . . . 2
2.0  Choosing The Proper Upgrade Kit . . . . . . . . . 3
3.0  Hardware / Items Supplied with  

Upgrade Kit  . . . . . . . . . . . . . . . . . . . . . . . . . . 3

4.0  Tools Required (not supplied)  . . . . . . . . . . . . 3
5.0  Installation Preparation  . . . . . . . . . . . . . . . . . 3
6.0  Installation Procedure  . . . . . . . . . . . . . . . . . . 3
7.0  Mounting the Module  . . . . . . . . . . . . . . . . . . 5
8.0  Wiring Harnesses  . . . . . . . . . . . . . . . . . . . . . 5
9.0 Reassembly . . . . . . . . . . . . . . . . . . . . . . . . . . 6
10.0  Post Installation Testing . . . . . . . . . . . . . . . . . 7
11.0 Standards   . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

 

Effective May 2014
Supercedes April 2000

Instruction Booklet IL70C1080H03

Instructions for Field Installing Ground Fault Alarm/Power

Supply Modules into Digitrip 520M Equipped Eaton

Magnum and Magnum DS Circuit Breakers

Summary of Contents for 70C1081G01

Page 1: ...tion Preparation 3 6 0 Installation Procedure 3 7 0 Mounting the Module 5 8 0 Wiring Harnesses 5 9 0 Reassembly 6 10 0 Post Installation Testing 7 11 0 Standards 8 Effective May 2014 Supercedes April...

Page 2: ...02C83G01 Shown Figure 2 Wiring Diagram for 520M Models and Ground Alarm Power Supply Modules 1 1 Auxiliary Power Ground Alarm When the module is wired as shown in Figure 2 it will provide an auxiliary...

Page 3: ...reparation 5 1 Remove Breaker from Line Ascertain that the breaker is completely powered down during the Ground Alarm Power Supply module installation If you are unsure as to whether or not the unit i...

Page 4: ...hor the steel trip deck plate into the mounting boss Be careful not to damage the Trip Indicator Assembly and Over Current Trip Switch Bell Alarm if your breaker contains this option Note N Observe ho...

Page 5: ...T THAT THE TIE WRAPS ARE TRIMMED AND THAT THE NEW HARNESSES AND EXISTING WIRING BE TUCKED NEATLY BACK INTO THE BREAKER FRAME LOOSE OR STRAY WIRES MIGHT INTERFERE WITH PROPER FIT AND ALIGNMENT OF THE T...

Page 6: ...th the sockets in the cavity The plug should fit with a slight insertion force Now or If the rating plug was left inside the trip unit use a 0 125 3 2 mm wide screwdriver to tighten the M4 screw until...

Page 7: ...following tests 10 4 2 Secondary Injection Test An AC current of 1 Amp input can be injected onto the breaker secondary contacts B 4 and B 5 This will trigger the Ground Alarm indicator to function a...

Page 8: ...test kit to initiate a ground trip and verify the alarm contact closure and breaker trip action The test port is located on the front left hand corner of the Trip Unit To access the port remove the pl...

Page 9: ...Booklet IL70C1080H03 Effective May 2014 Instructions for Field Installing Ground Fault Alarm Power Supply Modules into Digitrip 520M Equipped Eaton Magnum and Magnum DS Circuit Breakers EATON www eat...

Page 10: ...purposes and should not be considered all inclusive If further information is required you should consult an authorized Eaton sales representa tive The sale of the product shown in this literature is...