Effective May 2010

2C14990H02

05/10 AWA1230-2460

Vertical adapters 800/1600A on fixed

IZM low voltage circuit breakers

 warning

(1) Only qualified electrical persOnnel shOuld 

be permitted tO wOrk On the equipment.  

(2) always de-energize primary and  

secOndary circuits if a circuit breaker  

cannOt be remOved tO a safe wOrk lOcatiOn. 

(3) all circuit breakers shOuld be switched  

tO the Off pOsitiOn and mechanism springs 

discharged. 

failure tO fOllOw these steps fOr all  

prOcedures described in this instructiOn  

leaflet cOuld result in death, bOdily injury,  

Or prOperty damage.

 warning

the instructiOns cOntained in this awa and On 

prOduct labels have tO be fOllOwed. Observe 

the five safety rules: 

–   discOnnecting 

–   ensure that devices cannOt be  

  accidentally restarted 

–   verify isOlatiOn frOm the supply 

–   earthing and shOrt-circuiting 

–   cOvering Or prOviding barriers tO  

  adjacent live parts 

discOnnect the equipment frOm the supply. 

use Only authOrized spare parts in the repair 

Of the equipment. the specified maintenance 

intervals as well as the instructiOns fOr 

repair and exchange must be strictly adhered 

tO prevent injury tO persOnnel and damage tO 

the switchbOard.

Section 1: General information

The vertical adapter bolts directly to the rear  

primary terminal pads. This adapter will  

not accommodate cable adapters, only bus  

connections. A three-pole breaker will use a set  

of six adapters (eight for four-pole). All required 

mounting hardware is provided. Torque all bolts  

to 37–43 ft-lbs (50–58 Nm).

Section 2: Installation of  

vertical adapters

To install the vertical adapters, proceed with the 

following two steps:

Step 1:

 Assemble as shown with the hardware 

provided. Assembly to a load conductor is  

demonstrated.

Figure 1. Step 1

Load 

Conductor

M10 x 45 

Hex Bolt

Conical Spring 

Washer

Flat Washer

Vertical Adapter

Flat Washer

M10 Hex Nut

Summary of Contents for 800A

Page 1: ...ircuiting Covering or providing barriers to adjacent live parts Disconnect the equipment from the supply Use only authorized spare parts in the repair of the equipment The specified maintenance intervals as well as the instructions for repair and exchange must be strictly adhered to prevent injury to personnel and damage to the switchboard Section 1 General information The vertical adapter bolts d...

Page 2: ...Subject to alterations 05 10 AWA1230 2460 Z8694 Moon Doku Heng Printed in USA 05 10 05 10 AWA1230 2460 Effective May 2010 Step 2 Complete the installation of all vertical adapters as shown paying particular attention to the positioning of the adapters on the line and load conductors Figure 2 Step 2 Mount on Top of Line Conductor Mount on Bottom of Load Conductor ...

Page 3: ...ten Freischalten Gegen Wiedereinschalten sichern Spannungsfreiheit feststellen Erden und Kurzschließen Benachbarte unter Spannung stehende Teile abdecken oder abschranken Das Gerät ist vom Netz zu trennen Es dürfen nur vom Hersteller zugelassene Ersatzteile verwendet werden Die vorgeschriebenen Wartungsintervalle sowie die Anweisungen für Reparatur und Austausch sind unbedingt einzuhalten um Schäd...

Page 4: ...10 AWA1230 2460 Gültig ab Mai 2010 Schritt 2 Vervollständigen Sie den Anbau der vertikalen Anschlüsse wie in Abbildung 2 gezeigt Die vertikalen Anschlüsse werden an der Einspeiseseite oberhalb der oberen Anschlussleisten und an der Abgangsseite unterhalb der unteren Anschlussleisten befestigt Abbildung 2 Schritt 2 Einspeiseseite Montage der Adapter oberhalb der Anschlussleiste Abgangsseite Montage...

Reviews: