Seismic Data Requirements for Eaton UPS Equipment Installation User’s Guide 164000050—Rev 05
17
44..22
C
Ceenntteerr ooff G
Grraavviittyy
For seismic calculations, the center of gravity can be approximated using the dimensions in
with
respect to the left side bracket's front mounting hole (x,y,z origin).
Table 9. 9395/P/XC Unit Center of Gravity Specifications
Product
Type
X (left to right)
Y (front to rear)
Z (bottom to top)
9395
275 kVA UPS
856 mm
452 mm
956 mm
275 kVA UPS and FI-UPM
1063 mm
461 mm
943 mm
550 kVA UPS
1140 mm
475 mm
929 mm
550 kVA UPS and FI-UPM
1406 mm
475 mm
928 mm
825 kVA UPS
2160 mm
460 mm
870 mm
825 kVA UPS (2X-UPM)
1823 mm
455 mm
868 mm
825 kVA UPS (2X-UPM and
FI-UPM)
2011 mm
460 mm
882 mm
1100 kVA or 825 kVA and FI-
UPM
2388 mm
462 mm
880 mm
225-550 kVA MBM
431 mm
323 mm
966 mm
275 kVA UPS and MBM
1409 mm
412 mm
959 mm
550 kVA UPS and MBM
1768 mm
442 mm
937 mm
9395P
300 kVA UPS
856 mm
452 mm
956 mm
300 kVA UPS and FI-UPM
1063 mm
461 mm
943 mm
300 kVA UPS (2X-UPM)
1063 mm
461 mm
943 mm
600 kVA UPS
790 mm
360 mm
918 mm
600 kVA UPS and FI-UPM
1526 mm
360 mm
918 mm
600 kVA UPS (2X-UPM)
1085 mm
360 mm
918 mm
600 kVA UPS (FL-UPM and
2X-UPM)
1821 mm
360 mm
918 mm
900 kVA UPS (FL-UPM and
2X-UPM)
2119 mm
362 mm
918 mm
900 kVA UPS (FL-UPM and
3X-UPM)
2477 mm
362 mm
918 mm
900 kVA UPS (2X-UPM)
1850 mm
357 mm
850 mm
900 kVA UPS (3X-UPM)
2172 mm
357 mm
850 mm
1200 kVA UPS (3X-UPM)
2444 mm
361 mm
875 mm
1200 kVA UPS (4X-UPM)
2444 mm
365 mm
915 mm
9395XC
1500 kW (HD) UPS
1553 mm
383 mm
780 mm
1500 kW (LD) UPS
1721 mm
384 mm
784 mm
Eaton 9395, 9395P and 9395XC Foundation Plan and Mounting Requirements