Proper mounting of the equipment is the single most important factor in withstandi ng a seismic event. The
foundation must be level and continuous under the entire assembly. The foundation must be designed to
withstand the reaction loads imposed on it by the equipment during a seismic event. At a minimum, the
foundation must be designed to accommodate the tensile strength of the hardware indicated in
.
The anchoring system should be put in place prior to equipment installation to reduce effort associated with
anchoring. Welding to embedded steel members is acceptable provided the strength of the welds is
comparable to the mounting bolts.
The user is responsible for compliance with all local seismic codes.
N
NO
OT
TE
E
Anchoring hardware is not provided with Eaton seismic mounting kits because the type
of hardware is dependant on the foundation construction and composition.
Table 7. 9395/P/XC Unit and Fastener Requirements from Unit to Floor
Product
Type
Bolt Type and Size
Torque
Quantity
9395
275 kVA UPS
Class 8.8, M12
83 Nm
61 lb-ft.
8
275 kVA UPS and FI-UPM
12
550 kVA UPS
8
550 kVA UPS and FI-UPM
14
825 kVA UPS
16
825 kVA UPS (2X-UPM)
14
825 kVA UPS (2X-UPM and FI-UPM)
20
1100 kVA or 825 kVA and FI-UPM
22
225-550 kVA MBM
8
275 kVA UPS and MBM
12
550 kVA UPS and MBM
14
9395P
300 kVA UPS
Class 8.8, M12
83 Nm
61 lb-ft.
8
300 kVA UPS and FI-UPM
12
300 kVA UPS (2X-UPM)
14
600 kVA UPS
8
600 kVA UPS and FI-UPM
14
600 kVA UPS (2X-UPM)
12
600 kVA UPS (FL-UPM and 2X-UPM)
12
900 kVA UPS (FL-UPM and 2X-UPM)
14
900 kVA UPS (FL-UPM and 3X-UPM)
14
900 kVA UPS (2X-UPM)
14
Eaton 9395, 9395P and 9395XC Foundation Plan and Mounting Requirements