26
InsTALLATIon And oPerATIon MAnuAL
25-16330-B December 2019 www.eaton.com
Technical Specification
Auxiliary 24V supply
Nominal Voltage
20.4V - 29.0V
Fuse (PTC3)
300 mA polyswitch
Maximum current
30 mA
Max Cable Length
2km
Min Recommended cable size (csa)
1mm
2
This output is not to be used for Fire protecting equipment or Fire alarm routing Equipment
Any power taken from the alarm system will affect the standby duration
Mechanical specification
Weight including batteries
10.6 Kg
Weight excluding batteries
5.3 Kg
Dimensions (Standard batteries)
400 mm (L) x 320 mm (H) x 170 mm (D)
Type of Material (backbox)
Mild Steel (Powder Coated)
Type of Material (facia)
PC/ABS
Flammability Rating
UL 94 V0
Total Number of knockouts
24
Diameter of knockout
20 mm
Cable specification
Minimum cross-sectional area
1mm
2
Maximum cross-sectional area
4mm
2
Recomended cable type
FIRETUF FP200 2.5 mm
2
csa
CAuTIon
TerMInAL BLoCKs: do noT use eXCessIVe ForCe WHen TIGHTenInG THe
sCreWs on THe TerMInAL BLoCK
Optional Functions as per EN54 Parts 2 & 4
The panel is approved to EN54 Parts 2 & 4 including all the options in this section
which can be selected as required . On page 33 is a typical system wiring diagram,
which shows the recommended connections for the equipment described in
this section .
Panel Inputs
Class Change: (Option not required by EN54)
A pair of terminals are provided for class change . By shorting these terminals
together (e .g . Switch, Time clock) the alarm will sound (panel so loop
sounders only) . The Panel will not indicate a Fire . The alarm will cancel when the
short circuit is removed .