SPECIFICATIONS
EATON
Powerware
®
9125 Two-in-One UPS (2500/3000 VA) User’s Guide
S
164201374 Rev D
www.powerware.com
61
Table 7. Weights and Dimensions
UPS
Extended Battery Module
Dimensions
(WxDxH)
43.2
×
60.7
×
8.9 cm
17.0
”
×
23.9
”
×
3.5
”
(2U)
43.2
×
60.7
×
8.9 cm
17.0
”
×
23.9
”
×
3.5
”
(2U)
Weights
37 kg (81.5 lb)
42.5 kg (93 lb)
Table 8. Environmental and Safety
120V Models
208V Models
230V Models
Operating Temperature
0°C to 40°C (32°F to 104°F)
Optimal battery performance: 25°C (77°F)
Storage Temperature
0°C to 25°C (32°F to 77°F)
Transit Temperature
-25°C to 55°C (-13°F to 131°F)
Relative Humidity
5–95% noncondensing
Operating Altitude
Up to 3,000 meters above sea level
Transit Altitude
Up to 10,000 meters above sea level
Audible Noise
Less than 45 dBA Normal mode, typical load
Less than 50 dBA Battery mode
Surge Suppression
IEEE C62.41 Category B
IEEE C62.41 Category B
IEC 61000-4-5
IEC 61000-4-5
Safety Conformance
UL 1778, UL 497A
CSA C22.2, No. 107.1, 107.2
NOM-019-SCFI
UL 1778, UL 497A
NOM-019-SCFI
IEC 60950-1; EN 62040-1-1
IEC 60950-1; EN 62040-1-1
Agency Markings
cULus, NOM-NYCE
cULus, NOM-NYCE, CE,
TÜV-GS (G models only)
CE, TÜV-GS
EMC (Class A)
FCC Part 15, ICES-003
FCC Part 15, ICES-003
EN 50091-2, IEC 62040-2