SPECIFICATIONS
Eaton
®
9130 UPS (700–3000 VA) User's Guide
S
164201718 Rev 3
www.eaton.com/powerquality
80
Table 15. Electrical Input (Rackmount Models)
Model
Default Input
(Voltage/Current)
Selectable Input
Voltages
Voltage Range
at 100% Load
PW9130L700R-XL2U
120V / 5.8A
100*, 110**, 120, 127
80–138 Vac
PW9130L1000R-XL2U
120V / 8.3A
100*, 110**, 120, 127
80–138 Vac
PW9130L1500R-XL2U
120V / 12.5A
100*, 110**, 120, 127
80–138 Vac
PW9130L2000R-XL2U
120V / 16.7A
100*, 110**, 120, 127
90–138 Vac
PW9130L2500R-XL2U
120V / 20.8A
100*, 110**, 120, 127
90–138 Vac
PW9130L3000R-XL2U
120V / 25A
100*, 110**, 120, 127
90–138 Vac
PW9130G1000R-XL2U
208V / 4.8A
200*, 208**, 220, 230, 240
160–276 Vac
PW9130G2000R-XL2U
208V / 9.6A
200*, 208**, 220, 230, 240
180–276 Vac
PW9130G2500R-XL2U
208V / 12A
200*, 208**, 220, 230, 240
180–276 Vac
PW9130G3000R-XL2U
208V / 14.4A
200*, 208**, 220, 230, 240
180–276 Vac
PW9130i1000R-XL2U
230V / 4.3A
200*, 208**, 220, 230, 240
160–276 Vac
PW9130i1500R-XL2U
230V / 6.5A
200*, 208**, 220, 230, 240
160–276 Vac
PW9130i2000R-XL2U
230V / 8.7A
200*, 208**, 220, 230, 240
180–276 Vac
PW9130i3000R-XL2U
230V / 13.0A
200*, 208**, 220, 230, 240
180–276 Vac
PW9130G1000R-XL2UEU
208V / 4.8A
200*, 208**, 220, 230, 240
180–276 Vac
PW9130G2000R-XL2UEU
208V / 9.6A
200*, 208**, 220, 230, 240
180–276 Vac
PW9130G2500R-XL2UEU
208V / 12A
200*, 208**, 220, 230, 240
180–276 Vac
PW9130G3000R-XL2UEU
208V / 14.4A
200*, 208**, 220, 230, 240
180–276 Vac
PW9130G1000R-XL2UAU
240V / 4.4A
200*, 208**, 220, 230, 240
160–276 Vac
PW9130G1500R-XL2UAU
240V / 6.25A
200*, 208**, 220, 230, 240
160–276 Vac
PW9130G2000R-XL2UAU
240V / 8.7A
200*, 208**, 220, 230, 240
180–276 Vac
PW9130G3000R-XL2UAU
240V / 13.0A
200*, 208**, 220, 230, 240
180–276 Vac
* 100V and 200V are derated by 20%.