INSTALLATION
EATON
Powerware
®
9135 Two−in−One UPS (5000/6000 VA) User’s Guide
S
164201726 Rev 1
www.powerware.com
39
Recommended Downstream Protection (EU Models Only)
The indicated protection ensures discrimination for each output circuit
downstream of the UPS.
If these recommendations are not followed, protection discrimination is
not achieved and may result in a potential power interruption to the
connected devices.
UPS Power Rating
Downstream Circuit Breaker
EU Models Only
5000 VA
Z curve − 10A
C curve − 4A
6000 VA
Z curve − 10A
C curve − 6A
Required Cable Cross−Sections
Function
Wiring
EU Models
U Models
Terminal block cable
capacity
6 mm
2
, solid or stranded wire
(maximum 8 mm
2
or 8 AWG).
6 mm
2
, solid or stranded wire
(maximum 8 mm
2
or
10 AWG).
Capacity for ground/
earthing conductor
Continue to the following section, Connecting the Power Cables (EU