6.1 Native signal terminals
Table 19: Native signal terminals
Terminal
Pins
TB6 Pull chain
Pin 1: EXT Pullchain return
Pin 2: External pullchain
TB7 External CAN
connection
Pin 1: CAN cable shield grounding
Pin 2: CAN GND
Pin 3: CANBL
Pin 4: CANBH
TB8 CAN termina-
tion jumper
Pin 1: CAN termination 1
Pin 2: CAN termination 2
TB1 Customer
alarm, input
Pin 1: Signal input 5 return
Pin 2: Signal input 5
Pin 3: Signal input 4 return
Pin 4: Signal input 4
Pin 5: Signal input 3 return
Pin 6: Signal input 3
Pin 7:Signal input 2 return
Pin 8: Signal input 2
Pin 9: Signal input 1 return
Pin 10: Signal input 1
TB4 EPO
Pin 1: EPO normal closed
Pin 2: EPO normal closed return
Pin 3: EPO normal open
Pin 4: EPO normal open return
Note: There must be a jumper between Pin 3 and Pin 4 when a
normal closed EPO signal is used.
TB5 Relay, output
(30 Vac / 30Vdc, 5
A)
Pin 1: Relay normal open
Pin 2: Relay normal closed
Pin 3: Relay COM
The output relay configurations are shown in Figure
Eaton 91PS/93PS UPS 8–40 kW
User's and installation guide
©
Eaton Corporation plc 2018. All rights reserved.
Revision: 005
Document ID: P-164000493
73 (117)