9 Technical data
For a complete technical specification, contact your Eaton representative. Due
to continuous product improvement programs, specifications are subject to
change without notice.
9.1 Directives and standards
Safety
IEC 62040-1: Uninterruptible power systems (UPS) - Part
1: General and safety requirements for UPS
IEC 60950-1: Information technology equipment - Safety -
Part 1: General requirements (as referred through the IEC
62040-1)
EMC
IEC 62040-2: Uninterruptible power systems (UPS) - Part
2: Electromagnetic compatibility (EMC) requirements / Ed.
2
•
Emissions: category C2
•
Immunity: category C3
Performance & tests
IEC 62040-3: Uninterruptible power systems (UPS) - Part
3: Method of specifying the performance and test require-
ments
Environmental
IEC62040-4: Uninterruptible Power Systems (UPS) - Part
4: Environmental Aspects - Requirements and Reporting
IEC 62430: Environmentally conscious design for electrical
and electronic products
RoHS
2011/65/EU on the restriction of the use of certain hazard-
ous substances in electrical and electronic equipment
WEEE
2012/19/EU on waste electrical and electronic equipment
(WEEE)
ECO Design Directive
2009/125/EC establishing a framework for the setting of
eco-design requirements for energy-related products
Batteries
2006/66/EC on batteries and accumulators and waste bat-
teries and accumulators
Packaging
94/62/EC on packaging and packaging waste
9.2 UPS system input
Rated input voltage
220/380 V; 230/400 V; 240/415 V
Voltage tolerance, (Rectifier input)
230 V -15% / +20%
Voltage tolerance, (Bypass input)
230 V -15% / +10%
Rated input frequency
50 or 60 Hz
Frequency tolerance
40 to 72 Hz
Eaton 91PS/93PS UPS 8–40 kW
User's and installation guide
©
Eaton Corporation plc 2018. All rights reserved.
Revision: 005
Document ID: P-164000493
106 (117)