Setting
Description
Signal Input
Select signal input name and function or change contact polarity.
Relay Outputs
Configure the relay outputs.
Battery test
Change the power level and duration for battery test.
Bypass Limits
Change the bypass voltage or bypass frequency.
Screen Saver Time-
out
Change the screen saver timeout.
Meters
Change the meters format.
Lamp Test
Enable the lamp test.
HMI backlight
Adjust the backlight brightness.
Control P/W level 1
Change the level 1 password, or remove the password on level 1.
The default value is 1111.
Control P/W level 2
Change the level 2 password. The default value is 0101.
Reset statistics
Reset all statistics.
Minimum required
kVa
Change the minimum required kVa.
7.2 Signing in
If the level 1 password is enabled, you need to sign in.
1.
Press the lock icon in the top right corner of the screen.
2.
Type in your password and press OK.
You are signed in.
3.
Press Continue to return to the previous screen.
You have 3 attempts to type in the password. If an incorrect password is given
more than 3 times, you need to wait for 30 minutes before trying again.
To modify the user settings, you need to enter the level 2 password. For the
default passwords, see Section
.
7.3 System control instructions
7.3.1
Starting the UPS system in the double conversion mode
The UPS system can consist of a single UPS or several parallel UPSs. UPSs
with their MOB open are not considered as part of the system.
To start the UPS system:
1.
Open the UPS front door.
2.
Check that the rectifier input switch S1 closed.
3.
Check that the battery breaker CB1 is closed.
4.
Close the UPS front door.
Eaton 91PS/93PS UPS 8–40 kW
User's and installation guide
©
Eaton Corporation plc 2018. All rights reserved.
Revision: 005
Document ID: P-164000493
88 (117)