4
UPS installation plan and unpacking
4.1
About UPS installation
Use the following basic sequence of steps to install the UPS:
1.
Create an installation plan for the UPS system.
2.
Prepare your site for the UPS system.
3.
Inspect and unpack the UPS cabinet.
4.
Unload and install the UPS cabinet and wire the system.
5.
Complete the installation checklist provided in
Section 4.3 Installation
.
6.
Have authorized service personnel perform the preliminary operational
checks and startup.
NOTE: Startup and operational checks must be performed by an authorized
Eaton Customer Service Engineer or by other qualified service personnel
authorized by Eaton, or the terms specified in the Warranty (see Chapter
10.2 Whom to contact in case of Warranty) become void. This service is offered
as a part of the sales contract for the UPS. Contact service in advance (usually a
two-week notice is required) to reserve a preferred startup date.
4.2
Create an installation plan
Before you install the UPS system, read and understand how these instructions
apply to the system that you are going to install. Use the procedures and
illustrations in
Section 4.4 Site preparations
and
Chapter 5.1 About UPS system
to create a logical plan for installing the system.
4.3
Installation checklist
Table 7: Installation checklist
Action
Yes/No
All packing materials and restraints are removed from each cabinet.
Each cabinet in the UPS system is placed in its installed location.
A cabinet grounding kit / mounting kit is installed between any cabinets
that are bolted together.
All conduits and cables are properly routed to the UPS and any
ancillary cabinets.
© Eaton Corporation plc 2020. All rights reserved.