Installing the UPS
3−7
EATON
Powerware
®
9315 UPS (300–500 kVA) Installation Manual
S
164201118 Rev H
www.powerware.com
Installation Checklist
-
All packing materials and restraints have been removed from each cabinet.
-
Each cabinet in the UPS system is placed in its installed location.
-
A ground bond is installed between any cabinets that are bolted together.
-
All switchboards, conduits, and cables are properly routed to the UPS and auxiliary cabinets.
-
All power cables are properly terminated.
-
A ground conductor is properly installed.
-
If neutral connection is used, no other N−G bonds exist downstream from the UPS.
-
Battery cables and harness are terminated on E4 and E5.
-
Internal battery cabinet connections have been completed (bus bars, plugs, etc.).
-
Shunt trip signal wiring is connected from UPS to battery breaker(s).
-
Air conditioning equipment is installed and operating correctly.
-
The area around the installed UPS system is clean and dust-free. (It is recommended that the UPS be
installed on a sealed, concrete pad or a sealed, concrete floor.)
-
Adequate workspace exists around the UPS and other cabinets.
-
Adequate lighting is provided around all UPS equipment.
-
A 120V service outlet is located within 25 ft of the UPS equipment.
-
Each Remote Monitor Panel (RMP) is mounted in its installed location. (OPTIONAL)
-
The control wiring for each RMP is terminated inside the UPS cabinet. (OPTIONAL)
-
The Remote EPO device is mounted in its installed location and its wiring terminated inside the UPS
cabinet. (OPTIONAL)
-
Summary alarms and/or building alarms are wired appropriately. (OPTIONAL)
-
A RIM is mounted in its installed location and its wiring is terminated inside the UPS cabinet. (OPTIONAL)
-
A remote battery disconnect control is mounted in its installed location and its wiring is terminated inside
the UPS and battery cabinet. (OPTIONAL)
-
Circuit breakers with adjustable trip mechanisms adjusted to match site requirements.