DESCRIPTION:
DATE:
DRAWING NO:
INSTALLATION NOTES
SHEET:
REVISION:
G
164201118−1
NOTE:
Callout letter
and
map to drawing #164201118−4
,
,
,
E
A
B
C
F
D
G
E
F
H
,
,
,
A
E
H
G
,
4 of 19
020604
Customer Information
A−5
EATON
Powerware
®
9315 UPS (300–500 kVA) Installation Manual
S
164201118 Rev H
www.powerware.com
Table D. INPUT/OUTPUT Ratings & External Wiring Requirements for Powerware 9315 500 (0.9 pF)
Ratings
Units
Rating 60 Hz
Basic unit rating at
0.9 lagging pF load
kVA
kW
400
360
400
360
500
450
500
450
INPUT/OUTPUT
VOLTAGE
208
480
480
600
AC
INPUT
AC Input to UPS Rectifier
or Input
Transformer
(0.95min. pF)
3
O
, 1 gnd, 1 Neutral (Input Transformer only)
Minimum conductor size (number per
O
)
Minimum conductor size (number per
O
)
With Filter:
Amps*
1440
626
720
576
AWG or kcmil(ea)
600(5)
500(2)
350(3)
250(3)
Without Filter:
Amps*
N/A
715
850
658
AWG or kcmil(ea)
N/A
350(3)
500(4)
300(3)
*(Maximum amps includes full load current plus
battery recharge current)
AC
INPUT
AC Input to UPS Rectifier
from Input
Transformer
3
O
, 1 gnd
Minimum conductor size (number per
O
)
With Filter:
Amps
626
626
720
720
AWG or kcmil(ea)
500(2)
500(2)
350(3)
350(3)
AC
INPUT
AC Input to 5% Filter
3
O
, 1 Neutral, 1 gnd
Minimum conductor size (number per
O
)
With Filter:
Amps
N/A
626
720
N/A
AWG or kcmil(ea)
N/A
500(2)
350(3)
N/A
AC
INPUT
AC Input to UPS Rectifier
from 5%
Filter
3
O
, 1 gnd
Minimum conductor size (number per
O
)
With Filter:
Amps
N/A
626
720
N/A
AWG or kcmil(ea)
N/A
500(2)
350(3)
N/A
AC
INPUT
AC Input to UPS Bypass
or
Bypass
Transforme
r
Full Load Current
3
O
, (1) Neutral, (1) gnd
Minimum conductor size (number per
O
)
Amps
1110
480
601
480
AWG or kcmil(ea)
600(5)
250(3)
300(3)
250(3)
AC
INPUT
AC Input to UPS Bypass from Bypass Transform-
er
Full Load Current
3
O
, (1) Neutral, (1) gnd
Minimum conductor size (number per
O
)
Amps
560
N/A
N/A
640
AWG or kcmil(ea)
500(2)
N/A
N/A
300(3)
DC
INPUT
DC Input from Battery to UPS
(1) positive, (1) negative
Minimum conductor size (number per
O
)
VDC
Amps @ (1.8V/cell)
480
901
480
901
480
1120
480
1120
AWG or kcmil(ea)
See
Table E
See
Table E
See
Table E
See
Table E
AC
OUTPUT
AC Output to Output Transformer or Critical Load
Full Load Current
3
O
, (1) Neutral, (1) gnd
Minimum conductor size (number per
O
)
Amps
480
480
601
601
AWG or kcmil(ea)
250(3)
250(3)
350(3)
350(3)
AC
OUTPUT
AC Output from Output Transformer to Critical
Load
Full Load Current
3
O
, (1) Neutral, (1) gnd
Minimum conductor size (number per
O
)
Amps
1110
N/A
N/A
480
AWG or kcmil(ea)
600(5)
N/A
N/A
4/0(3)
ISO GND
Isolated Ground Connection to Grounding
Electrode system (Optional)
Minimum conductor size (number per
O
)
AWG or kcmil(ea)
1/0 (2)
Summary of Contents for 9315
Page 1: ...Powerware 9315 UPS 300 500 kVA Installation Manual ...
Page 97: ......