INSTALLATION NOTES
SHEET:
REVISION:
D
164201118−1
101598
NOTE: Customer ground, size 2/0, can be
run in any conduit listed in Table H.
7 of 19
Customer Information
A−8
EATON
Powerware
®
9315 UPS (300–500 kVA) Installation Manual
S
164201118 Rev H
www.powerware.com
Table G. Transformer and Filter Cabinet Power Cable Terminations
Terminal Function
Terminal
Function
Size of Pressure
Termination
Tightening
Torque
N-M (lb-in)
Int Hex
Size (In.)
AC Input to Input
Isolation Transformer
(480/480)
(as applicable)
E23
Phase A
4 − #2−600 kcmil
56.5 (500)
1/2
E24
Phase B
4 − #2−600 kcmil
56.5 (500)
1/2
E25
Phase C
4 − #2−600 kcmil
56.5 (500)
1/2
AC Output from Input
Isolation Transformer
(480/480)
(as applicable)
E26
Phase A
4 − #2−600 kcmil
56.5 (500)
1/2
E27
Phase B
4 − #2−600 kcmil
56.5 (500)
1/2
E28
Phase C
4 − #2−600 kcmil
56.5 (500)
1/2
AC Input to Input
Isolation Transformer
(208/480)
(as applicable)
E23
Phase A
4 − #2−600 kcmil
56.5 (500)
1/2
E24
Phase B
4 − #2−600 kcmil
56.5 (500)
1/2
E25
Phase C
4 − #2−600 kcmil
56.5 (500)
1/2
E22
Neutral
4 − #2−600 kcmil
56.5 (500)
1/2
AC Output from Input
Isolation Transformer
(208/480)
(as applicable)
E26
Phase A
4 − #2−600 kcmil
56.5 (500)
1/2
E27
Phase B
4 − #2−600 kcmil
56.5 (500)
1/2
E28
Phase C
4 − #2−600 kcmil
56.5 (500)
1/2
E29
Neutral
4 − #2−600 kcmil
56.5 (500)
1/2
AC Input to Input
Isolation Transformer
(600/480)
(as applicable)
E23
Phase A
4 − #2−600 kcmil
56.5 (500)
1/2
E24
Phase B
4 − #2−600 kcmil
56.5 (500)
1/2
E25
Phase C
4 − #2−600 kcmil
56.5 (500)
1/2
AC Output from Input
Isolation Transformer
(600/480)
(as applicable)
E26
Phase A
4 − #2−600 kcmil
56.5 (500)
1/2
E27
Phase B
4 − #2−600 kcmil
56.5 (500)
1/2
E28
Phase C
4 − #2−600 kcmil
56.5 (500)
1/2
AC Input to 5% Input
Filter (480/480)
(as applicable)
E23
Phase A
4 − #2−600 kcmil
56.5 (500)
1/2
E24
Phase B
4 − #2−600 kcmil
56.5 (500)
1/2
E25
Phase C
4 − #2−600 kcmil
56.5 (500)
1/2
AC Output from 5%
Input Filter (480/480)
(as applicable)
E26
Phase A
4 − #2−600 kcmil
56.5 (500)
1/2
E27
Phase B
4 − #2−600 kcmil
56.5 (500)
1/2
E28
Phase C
4 − #2−600 kcmil
56.5 (500)
1/2
AC Input to Output
Auto Transformer
(480/208)
(as applicable)
E23
Phase A
4 − #2−600 kcmil
56.5 (500)
1/2
E24
Phase B
4 − #2−600 kcmil
56.5 (500)
1/2
E25
Phase C
4 − #2−600 kcmil
56.5 (500)
1/2
AC Output from
Output Auto
Transformer (480/208)
(as applicable)
E26
Phase A
4 − #2−600 kcmil
56.5 (500)
1/2
E27
Phase B
4 − #2−600 kcmil
56.5 (500)
1/2
E28
Phase C
4 − #2−600 kcmil
56.5 (500)
1/2
E29
Neutral
8 − #2−600 kcmil
56.5 (500)
1/2