UPS CABINET
BATTERY
CRITICAL
LOAD
CABINET
(OPTIONAL)
RECTIFIER
INPUT FILTER
CB1
TO GROUND
AC
OUTPUT
TO
E4−5
TO
ADDITIONAL
BATTERY
CABINET
(OPTIONAL)
STATIC
SWITCH
BYPASS
CONTACTOR
(K4)
E9−12
ON INVERTER"
ON BYPASS"
MONITORING
RS−232
RS−485
REMOTE EPO
GENERATOR
INTERFACE
AC INPUT TO
UPS RECTIFIER
3 WIRE A−B−C
BUILDING ALARMS
E6−8
AC INPUT
TO BYPASS
3 OR 4 WIRE A−B−C
ROTATION
COMMUNICATIONS
PANEL
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
F
164201118−4
ONELINE DRAWINGS OF UPS SYSTEM
1 of 5
082806
INVERTER
OUTPUT
CONTACTOR
OUTPUT FILTER
(K3)
OUTPUT
TRANSFORMER
Y
BATTERY
FUSE
E1−3
ROTATION
NOTE 1: Optional jumper for single feed. Use
terminals E6, E7, and E8 for connection.
See Table A, Table D, Table C, or Table D
row for wire rating.
NOTE 2: A bypass neutral feeder must be supplied
when the output neutral is used.
If no
bypass neutral is supplied, the output
neutral is to be bonded to ground through a
minimum 3/0 copper conducter.
(See Table O, Table P, Table Q,
and Table R)
SEE NOTE 1
UPS SYSTEM WITH 480V INPUT,
SINGLE OR DUAL FEED
B
D
A
C
B
(OPTIONAL)
ISOLATED GROUND BUS
TO GROUNDING ELECTRODE SYSTEM
(OPTIONAL)
H
Customer Information
A−23
EATON
Powerware
®
9315 UPS (300–500 kVA) Installation Manual
S
164201118 Rev H
www.powerware.com