Installation
Eaton 9315/9390/9395/9395P Fixed Primary Sync Control Installation and Operation Manual P-164000023—Rev 03
3-15
3.3
Installation and Wiring with an Eaton 9390 UPS
To install and wire:
1.
Install the Eaton Fixed Primary Sync Control panel to the selected mounting location.
See Figure 2-1 on page 2-2 for mounting hole dimensions and Figure 2-2 on page 2-3 for conduit entrance
locations.
2.
Unfasten the front door latches and swing the door open.
3.
Complete all control wiring interconnections using Table 3-7 for wiring requirements.
Figure 3-2 shows the Eaton Fixed Primary Sync Control TB1 terminal block and ground terminal locations.
Figure 3-3 shows the TB1 terminal block wiring detail.
Figure 3-11 through Figure 3-12 show the typical locations of the UPS TB1, TB2, and TB6 interconnect
terminal blocks. Figure 3-13 shows the TB6 detail.
Refer to the applicable Eaton UPS Installation and Operation Manual listed in paragraph 1.3 on page 1-4 for
UPS cabinet terminal locations and assignments, termination requirements, conduit landing locations, and
terminal access instructions.
4.
Verify the jumper is installed between Sync Control terminal TB140 and TB141 (see Figure 3-3).
5.
When all wiring is complete, close the door and secure the latch.
CAUTION
When connecting the bypass and load voltage from another model UPS to an Eaton 9390 UPS
using the Eaton Fixed Primary Sync Control accessory, use Phase A, Phase B, and Neutral
connections from the other UPS. DO NOT connect the other model UPS Phase C bypass and load
voltage to the Sync Control connection point when connecting to an Eaton 9390 UPS.
NOTE
When installing wiring connections, conduit must be installed between the Eaton
Fixed Primary Sync Control and the UPS cabinet. Conduit also must be installed
between the Eaton Fixed Primary Sync Control and the customer's remote
monitoring system.
Summary of Contents for 9315P
Page 1: ...Eaton 9315 9390 9395 9395P Fixed Primary Sync Control Installation and Operation Manual...
Page 2: ......
Page 3: ...Eaton 9315 9390 9395 9395P Fixed Primary Sync Control Installation and Operation Manual...
Page 8: ...This page intentionally left blank...
Page 61: ......
Page 62: ...P 164000023 2 P 164000023 3...