Installation
Eaton 9315/9390/9395/9395P Fixed Primary Sync Control Installation and Operation Manual P-164000023—Rev 03
3-7
Table 3-3. Eaton 9315 UPS System Control Wiring Interconnections for Single Module 30500 kVA UPS (Primary to Sync Control)
From Secondary UPS (9315)
To Sync Control
Function
Note
TB65 TB110
BYPASS VOLTAGE
14 AWG
Twist Together
TB66 TB111
TB611 TB17
LOAD VOLTAGE
14 AWG
Twist Together
TB612 TB18
TB613 TB19
Remove the following jumpers, if connected, from UPS
module terminal block TB6 when installing the Sync Control
FROM
TB65
TB66
TB67
TO
TB68
TB69
TB610
Table 3-4. Eaton 9315 UPS System Control Wiring Interconnections for 750 kVA UPS (Primary to Sync Control)
From Secondary UPS (9315)
To Sync Control
Function
Note
CUSTTB21
TB110
BYPASS VOLTAGE
14 AWG
Twist Together
CUSTTB22
TB111
CUSTTB25
TB17
LOAD VOLTAGE
14 AWG
Twist Together
CUSTTB26
TB18
CUSTTB27*
TB19
*Requires installation of CK155011100 to have 750 kVA module as the primary for any other Eaton 9315 series system other than another 750 kVA unit.
Remove the following jumpers, if connected, from UPS
module terminal block TB6 when installing the Sync Control
FROM
CUSTTB21
CUSTTB22
TO
CUSTTB23
CUSTTB24
Summary of Contents for 9315P
Page 1: ...Eaton 9315 9390 9395 9395P Fixed Primary Sync Control Installation and Operation Manual...
Page 2: ......
Page 3: ...Eaton 9315 9390 9395 9395P Fixed Primary Sync Control Installation and Operation Manual...
Page 8: ...This page intentionally left blank...
Page 61: ......
Page 62: ...P 164000023 2 P 164000023 3...