Installation
3-16
Eaton 9315/9390/9395/9395P Fixed Primary Sync Control Installation and Operation Manual
P-164000023—Rev 03
Table 3-7. Eaton 9390 UPS System Control Wiring Interconnections
From Secondary UPS (9390)
To Sync Control
Function
Note
TB61 TB14
Bypass Voltage
14 AWG
Twist Together
TB62
TB15
TB63
TB16
TB64
TB113
Load Voltage
14 AWG
Twist Together
TB65
TB114
TB66
TB115
TB67
–
NOT USED
–
TB68
–
NOT USED
–
TB69
TB117
Bypass Voltage Phase B Return
14 AWG
TB610
–
NOT USED
–
TB10 (AS400 Relay Card)
TB11
On Bypass Common
14 AWG
Twist Together
TB11 (AS400 Relay Card)
TB12
On Bypass NO
P55
TB122
Building Alarm 5 (MiniCSB)
(Transfer to Bypass Disable)
14 AWG
Twist Together
P56
TB123
Building Alarm 5 Return
P57
TB126
Building Alarm 6 (MiniCSB)
(Sync Control Trouble)
14 AWG
Twist Together
P58
TB127
Building Alarm 6 Return
From Primary UPS (9390)
To Sync Control
Function
Note
TB61 TB110
Bypass Voltage
14 AWG
Twist Together
TB62
TB111
TB63
TB112
TB64
TB17
Load Voltage
14 AWG
Twist Together
TB65
TB18
TB66
TB19