OPERATION
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide
S
164201642 Rev C
www.eaton.com/powerquality
77
Table 10. User Settings (continued)
Default Setting
Available Settings
Description
Battery Charging
ABM cycling/constant
ABM cycling
Automatic Battery Tests
Enabled/Disabled
Enabled automatically runs the battery test
once a month.
Enabled
Full Power Battery Test
Enabled/Disabled
Enabled
Number of Battery Strings
0 through 22
NOTE Options 3 through 22 are not used.
Option 2 optimizes battery recharging.
2 strings
Battery Capacity
1 through 65535 watts per cell
34 W/cell
Battery Low Alarm Level
1.750 through 1.950 volts per cell
1.880 V/cell
Set Nominal Output Voltage
Output: [120V/208V] [127V/220V]
NOTE The 127V/220V option is not used.
120V/208V
Bypass Voltage High Limit
+1 t20% (1% increments)
120V +10%
Bypass Voltage Low Limit
-1 through -20% (1% increments)
120V -15%
Nominal Output Frequency
50 Hz or 60 Hz
60 Hz
Synchronization
Enabled/Disabled
Enabled
Synchronization Window
±
0.5 through
±
3.0 Hz
(0.1 Hz increments)
±
2.0 Hz
Unsynchronized Transfer to Bypass
Allowed/Not Allowed
Not Allowed
Output Frequency Slew Rate
0.1 though 5 hertz per second
(0.1 Hz increments)
0.5 Hz/s
Usage of Bypass
Enabled/Disabled
Enabled
Transfer to Bypass When Overload
After a delay/Immediately
After a delay
Automatic Start Delay
-1 through 32767 seconds
(-1 means disabled)
0s
Control Commands from X-Slot1
Allowed/Disabled
Allowed
Control Commands from X-Slot2/Serv
Allowed/Disabled
Allowed
X-Slot Signal Input Activation Delay
0 through 65 seconds
5s
Input signal delayed shutdown delay
1 through 65535 seconds
120s
Site Wiring Fault Notice
Enabled/Disabled
Enabled