Chapter 13
Troubleshooting
The Eaton 9355-F47 Unirom UPS is designed for durable, automatic
operation and also alerts you whenever potential operating problems
may occur. Usually the alarms shown by the control panel do not mean
that the output power is affected. Instead, they are preventive alarms
intended to alert the user. Use the following troubleshooting chart to
determine the UPS alarm condition.
NOTE
Battery functions are disabled when an ultracapacitor module is installed.
Typical Alarms and Conditions
The following table describes typical alarms and conditions; check the
Event Log through the control panel for a list of active alarms. If an alarm
appears with a service code, please contact the Help Desk (see
page 103).
Alarm or Condition
Possible Cause
Action
On Battery
LED is on.
1 beep every second.
A utility failure has occurred and the
UPS is in Battery mode.
The UPS is powering the equipment with battery
power. Prepare your equipment for shutdown.
Battery Low
LED is on.
Continuous beep for
10 seconds.
The battery is running low.
Five minutes or less of battery power remains
(depending on load configuration and battery
charge). Save your work and turn off your
equipment.
When utility power is restored, the UPS restarts
automatically, provides power to the load, and
charges the battery.
Battery Breaker
LED is on.
1 beep every second.
The UPS does not recognize the
internal batteries.
Verify the battery circuit breaker is in the ON
position. If the condition persists, contact your
service representative.