UPS SETUP
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide
S
164201642 Rev C
www.eaton.com/powerquality
16
Floor Loading
When planning the installation, consider the UPS weight for floor
loading. The strength of the installation surface must be adequate for
point and distributed loadings. The approximate weights are shown in
the following table. Figure 4 shows the leveling feet and casters.
Standard Model Floor Loadings
Eaton 9355-F47
Unirom
Maximum Weight
(without Batteries or
Ultracapacitor)
Maximum Weight
(with Both Battery
Trays or Ultracapacitor)
Point Loading
lb/in
2
(kg/cm
2
)
UPS
190 lb (86.2 kg)
410 lb (186 kg)
103 (7.3)
10.43”
(265 mm)
8.15”
(207 mm)
1.14”
(29 mm)
9.31”
(236.5 mm)
18.62”
(473 mm)
22.28”
(566 mm)
1.83”
(46.5 mm)
Leveling Feet (4x)
Casters (6x)
Figure 4. Leveling Feet and Casters
Clearances
The following clearances are recommended for the Eaton 9355-F47
Unirom UPS:
From Front of Cabinet
36
”
(91.4 cm) working space
From Back of Cabinet
6
”
(15.2 cm)