UPS MAINTENANCE
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide
S
164201642 Rev C
www.eaton.com/powerquality
89
8.
Disconnect the two battery trays by disconnecting the black
connector from the top tray from the red connector from the
bottom tray. See Figure 45.
Figure 45. Disconnecting the Battery Trays
9.
Place an adjustable-height table (customer-provided) near the UPS.
Adjust the table so its height is level with the top battery tray.
10.
Place the spike of a T-bar handle through one of the holes on the
top battery tray lip. Pull the tray onto the table.