Eaton 9355 Parallel UPS (10/15 kVA) User's Guide 164201601—Rev E0
Table 6. User Settings (Continued)
Description
Available Settings
Default Setting
(see
4 strings for UPS-64 models
Battery Capacity
1 through 65535 watts per cell
34 W/cell
Battery Low Alarm Level
1.750 through 1.950 volts per cell
1.880 V/cell
Bypass Voltage High Limit
+1 t20% (1% increments)
120V +10%
Bypass Voltage Low Limit
-1 through -20% (1% increments)
120V -15%
Nominal Output Frequency
50 Hz or 60 Hz
60 Hz
Synchronization
Enabled/Disabled
Enabled
Synchronization Window
±0.5 through ±3.0 Hz
(0.1 Hz increments)
±2.0 Hz
Unsynchronized Transfer to Bypass
Allowed/Not Allowed
Not Allowed
Output Frequency Slew Rate
0.1 though 5 hertz per second
(0.1 Hz increments)
0.5 Hz/s
Usage of Bypass
Enabled/Disabled
Enabled
Transfer to Bypass When Overload
After a delay/Immediately
After a delay
Automatic Start Delay
-1 through 32767 seconds
(-1 means disabled)
0s
Control Commands from X-Slot1
Allowed/Disabled
Allowed
Control Commands from X-Slot2/Serv
Allowed/Disabled
Allowed
X-Slot Signal Input Activation Delay
0 through 65 seconds
5s
Input signal delayed shutdown delay
1 through 65535 seconds
120s
Site Wiring Fault Notice
Enabled/Disabled
Enabled
Reset Custom Event Settings
0 through 32
Total: 0/32
Auto Output Configuration
Enabled/Disabled
Enabled for initial startup
Disabled after initial startup
66..22
IInniittiiaall S
Sttaarrttuupp
Startup and operational checks must be performed by an authorized Eaton Customer Service Engineer, or the
warranty terms specified on the product's resources page become void. See
for details.
This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in
advance (a minimum two-week notice is required) to reserve a preferred startup date.
WARNING
Only qualified service personnel (such as a licensed electrician) should perform the UPS installation. Initial
startup must be performed by an authorized Eaton Customer Service Engineer. Risk of electrical shock.
Summary of Contents for 9355 Series
Page 1: ...p n 164201601 Revision E0 10 15 kVA User s Guide Eaton 9355 Parallel UPS ...
Page 4: ......
Page 10: ...x Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 List of Tables ...
Page 18: ...8 Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 Safety Warnings ...
Page 54: ...44 Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 UPS System Installation ...
Page 68: ...58 Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 Operation ...
Page 72: ...164201601E0 164201601 E0 ...