Eaton 9355 Parallel UPS (10/15 kVA) User's Guide 164201601—Rev E0
The nominal input/output voltages are:
•
120/208 or 127/220 Vac
Output overcurrent protection and disconnect switch must be provided by others.
WARNING
Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and initial
startup. Risk of electrical shock.
To hardwire the parallel system:
1.
Verify that the electrical connections to the installation site have been properly installed.
2.
A wall-mounted, user–supplied, readily–accessible disconnection device must be incorporated in the input
wiring.
Compare the circuit breaker ratings to the ones in
NOTE
To accommodate the feature of easy system expandability, it is recommended that
initial installation of the Eaton 9355 UPS contain wiring to support the maximum
capacity of the UPS cabinet.
3.
Switch off utility power to the distribution point where the parallel tie cabinet and UPSs will be connected.
Be absolutely sure there is no power.
4.
Determine your equipment's grounding requirements according to your local electrical code.
5.
Remove the parallel tie cabinet front cover (see
).
Figure 11. Version 1 Parallel Tie Cabinet Front Cover
6.
Remove the internal cover to gain access to the breakers (see
Summary of Contents for 9355 Series
Page 1: ...p n 164201601 Revision E0 10 15 kVA User s Guide Eaton 9355 Parallel UPS ...
Page 4: ......
Page 10: ...x Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 List of Tables ...
Page 18: ...8 Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 Safety Warnings ...
Page 54: ...44 Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 UPS System Installation ...
Page 68: ...58 Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 Operation ...
Page 72: ...164201601E0 164201601 E0 ...