Responding to System Events
12-6
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201604 Rev B
powerware.com
NOTICES
Indication
Log*
Relay
Phone
Horn
Message
Input AC Over Voltage
1
No
No
HA Information Only
Input AC Over Voltage OK
Off
No
No
HA Condition Cleared
Input AC Under Voltage
1
No
No
HA Information Only
Input AC Under Voltage OK
Off
No
No
HA Condition Cleared
Input Phase Rotation
1
No
No
HA Information Only
Input Phase Rotation OK
Off
No
No
HA Condition Cleared
Input Under or Over Frequency
1
No
No
HA Information Only
Input Under or Over Frequency OK
Off
No
No
HA Condition Cleared
Inv Under or Over Frequency
1
No
No
HA Information Only
Inv Under or Over Frequency OK
Off
No
No
HA Condition Cleared
Inverter AC Over Voltage
1
No
No
HA Information Only
Inverter AC Over Voltage OK
Off
No
No
HA Condition Cleared
Inverter AC Under Voltage
1
No
No
HA Information Only
Inverter AC Under Voltage OK
Off
No
No
HA Condition Cleared
Inverter Off Command
1
No
No
A
Information Only
Inverter On Command
1
No
No
HA Information Only
Inverter Output Overcurrent
1
No
No
HA Information Only
Inverter Phase Rotation
1
No
No
HA Information Only
Inverter Phase Rotation OK
Off
No
No
HA Condition Cleared
Load Dumped (Load Power Off)
1
1
No
HA Investigate UPS
Load Dumped (Load Power Off) OK
Off
No
No
HA Condition Cleared
Load Off Command Executed
1
No
No
HA Information Only
Load Power On Command
1
No
No
HA Information Only
Load Power On Command Received
1
No
No
HA Information Only
Loss of Redundancy
1
No
No
HA Information Only
Loss of Redundancy OK
Off
No
No
HA Condition Cleared
Maintenance Bypass Mode
1
No
No
HA Information Only
Modem Call Completion Failed
1
No
No
HA Information Only
Neutral Current Limit
1
No
No
HA Information Only
Neutral Current Limit OK
Off
No
No
HA Condition Cleared
Non-Volatile Memory Failure
1
No
No
A
Information Only
Non-Volatile Memory Failure OK
Off
No
No
A
Condition Cleared
Output AC Over Voltage
1
No
No
HA Information Only
Output AC Over Voltage OK
Off
No
No
HA Condition Cleared
*Log codes indicate where the UPS records the event: H = History log; HA = History and Active logs; and
A = Active log only.
Summary of Contents for 9390 UPS 100160 kVA
Page 1: ...Powerware 9390 UPS 100 160 kVA Installation and Operation Manual...
Page 225: ......
Page 226: ...164201604B 164201604 B...