1 of 1
OPTIONAL POWERWARE REMOTE
EMERGENCY POWER-OFF
091505
A
164201604---10
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
114.3
(4.50)
115.8
(4.56)
11.9
(0.47)
95.3
(3.75)
SQUARE
88.9
(3.50)
1/2 in. Knockout Pattern
typ. 5 sides
TO UPS
TO OTHER
EQUIPMENT
Dimensions are in millimeters [inches]
NOTE:
1. Conduit and wiring between the
Remote Emergency Power-off (REPO)
and the UPS to be supplied by the
customer.
2. Maximum distance between the
Remote EPO and the UPS not to exceed
500 feet.
3. Maximum wire size #14 AWG.
Minimum wire size #22 AWG.
Installation Information
A-50
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201604 Rev B
powerware.com