A-5
6.
The clearances required around the UPS cabinet are shown in Table C.
Table C. 9390 and 9390IT UPS Cabinet Clearances
From Top of Cabinet
Minimum clearance over the UPS cabinet is
457.2 mm (18 inches) for ventilation
From Front of Cabinet
914.4 mm (36 inches) working space
From Back of Cabinet
None required
From Right Side of Cabinet
None required
From Left Side of Cabinet
76 mm (3 inches) for door swing
None for 9390IT UPS with internal batteries
7.
The basic environmental requirements for operation of the UPS system are:
Ambient Temperature Range:
0-40°C (32-104°F)
Recommended Operating Range:
20-25°C (68-77°F)
Maximum Relative Humidity:
95%, noncondensing
The UPS ventilation requirements are shown in Table D.
Table D. 9390 and 9390IT Air Conditioning or Ventilation Requirements During Full
Load Operation
Ratings
Voltage
Heat Rejection
BTU/hr
1000/hr (kg‐cal/hr)
Input
Output
20 kVA
208/220
208/220
5.9 (1.49)
20 kVA
380/400/415/480
380/400/415/480
5.5 (1.38)
30 kVA
208/220
208/220
8.9 (2.24)
30 kVA
380/400/415/480
380/400/415/480
8.2 (2.07)
40 kVA
208/220
208/220
11.8 (2.98)
40 kVA
380/400/415/480
380/400/415/480
10.9 (2.76)
50 kVA
208/220
208/220
14.8 (3.73)
50 kVA
380/400/415/480
380/400/415/480
13.7 (3.45)
60 kVA
208/220
208/220
17.7 (4.47)
60 kVA
380/400/415/480
380/400/415/480
16.4 (4.14)
80 kVA
208/220
208/220
23.6 (5.96)
80 kVA
380/400/415/480
380/400/415/480
21.9 (5.52)
Ventilation required for cooling air exhaust: approximately 472 liter/sec (1000 cfm).